Technical Specifications

990-1400A

Installation Guide APC BC300 Series 60kW 208/480V UPS

35

7.2

Battery Specifications

7.3

Dimensions/Weight

60kW

Nominal DC current - Amps

300

UL rating of terminal blocks - AWG

a

a.Terminal block has two positive and two negative

8 mm (=5/16”) studs, hardware provided. Lug re-
quired.
Conductor size may vary based on installation re-
quirements. Size all conductors per applicable
codes.

14 - 2/0

Nominal DC voltage

216

Nominal number of cells

108

Factory-set float charge voltage

b

b.Adjust the float charge voltage setting according

to the battery manufacturer’s recommendations.

246

Charger current limit - Amps

c

c.Programmable to lower level.

30

Inverter efficiency -% 100% load

75% load

50% load

25% load

92

92

90

87

BC300 Series UPS

60kW

Height

59.1 inches

Width

39.4 inches

Depth

31.7 inches

Weight 2214