Installation

990-1400A

Installation Guide APC BC300 Series 60kW 208/480V UPS

15

Figure 7 Single Line Diagram 480V

NOTICE!

Size utility input overcurrent protection device as per applicable codes. See below table for utility
input voltage and current ratings.

Notes:
1. Must be 3- or 4-wire + Ground
2. Must be 3- or 4-wire + Ground cabling
provided by others.
3. Input overcurrent protection is based on
80% rating - any deviation, please contact
APC.
4. F1, F2, F3 = 75A
5. F4, F5, F6 = 110A
6. All AC power cabling is 3- or 4-wire +
Ground at 480VAC 3-phase.
7. UPS output cables and input cables must
be in separate conduits.
8. Power wiring and control wiring must be in
separate conduits.
9. See installation manual for battery
information.
10. Installation must comply with all
applicable national and local codes.

Utility Source (provided by others)

480V 3 or 4 Wire + Ground

MIB

Service
Bypass
Panel

F4, 5, 6

UIF

Q001

UIS

UPS

F1, 2, 3

UOF

Q002

UOS

Q003

BS

UPS System Output

480V 3 or 4 Wire + Ground

60kW

72A

72A

72A

95A

95A

300A

130AT

400AT