-For sidewall terminations-

For multiple sidewall exhaust terminations (e.g. Multi-

Unit Systems), an exhaust termination must be at least 1

ft. (305mm) away from another exhaust termination. An

exhaust termination must also be at least 2 ft. (610 mm)

away from an inside corner. (If the adjacent wall is less than

2 ft. (610 mm) of length, the minimum required distance

away from the inside corner will be equal to the length of

that adjacent wall.)

For multiple-unit, direct-vent sidewall terminations that

combine the intake and exhaust into a single penetration,

space each direct-vent termination at least 1 ft. (305 mm)

away from each other, no matter the orientation. A direct-

vent termination must also be at least 2 ft. (610 mm) away

from an inside corner. (If the adjacent wall is less than 2 ft.

(610 mm) of length, the minimum required distance away

from the inside corner will be equal to the length of that

adjacent wall.)

Installation

Exhaust

termination

Inside

corner

1 ft.

(305 mm) min

2 ft.

(610 mm) min

1 ft. (305 mm)

min

Combined

intake and

exhaust

termination

Inside

corner

1 ft.

(305 mm) min

2 ft.

(610 mm) min

1 ft. (305 mm)

min

Installation Manual

For direct-vent sidewall

terminations that use two

separate penetrations for

the intake and exhaust,

keep the termination

clearances shown in the

diagrams on the right.

Please follow all local and national codes in regards to proper termination

clearances. In the absence of such codes, the clearances below can be used as

guidelines. Local codes supersede these guidelines.

CAUTION

1 ft. (305 mm) min

0.5 ft

(159 mm) min

Exhaust

Intake

Exhaust

Intake

1 ft. (305 mm)

min

0.5 ft.

(159 mm) min

0.5 ft.

(159 mm)

min

Exhaust

Intake

Exhaust

Intake