Standard configuration: Out(1) is carbon monoxide output, Out(2) is carbon dioxide
output and Out(3) is relay output. Out(4) is error status OR Out(3) is open.

Out(1) = measuring signal for carbon monoxide concentration
Out(2) = measuring signal for carbon dioxide concentration
Out(3) = ON/OFF of demand of air quality. The relay is open in alarm situations and
at power loss. NOTE! There is a two minutes delay after start-up.
Out(4) = error status OR Out(3) open, carbon monoxide concentration > 35 ppm OR
carbon dioxide concentration > 1500 ppm. There is a two minutes delay after start-
up.

Figure 4 The control signal of air quality

# in

figure 4

Terminal

Standard

configuration

Standard settings

Standard function

1




2



Power (+)



Power ground (-)

24 VAC/DC+
(+-20%), 3W


24 VAC/DC-

2W without output load

The same ground reference has to
be used for the
CF8-W-Disp-CO
unit and for the control system!

3

Out(1)

0-10VDC

0-100 ppm CO

Measuring signal carbon monoxide

4

Out(2)

0-10VDC

0-2000 ppm CO

2

Measuring signal carbon dioxide

5

Unmarked Signal Ground (-)

Connected to G0 via PTC fuse

6

7

Relay



Closed


Open



< 30 ppm CO
< 1400 ppm CO

2


> 35 ppm CO
> 1500 ppm CO

2

Air control Delay two minutes after
start.

The green LED is lit

The relay is open in alarm situations
and at power loss. The red LED is lit
and the green is not lit.

8

Out(4)
Open
collector

Open



Closed

No error detected
AND normal gas
concentrations

Error detected OR
high gas
concentrations

Error status Delay two minutes after
start.

The red LED is lit if an error OR high
gas concentrations are detected. If
an error is detected also the yellow
LED is lit

Table I. Default configuration of

CF8-W-Disp-CO.

~

+