beautypg.com

Led displays, Error messages, Io-extension – sk tu4-ioe-m12 – NORD Drivesystems TI 275281206 User Manual

Page 8

background image

IO-Extension

– SK TU4-IOE-M12

8

TI 275281206 - 4912

LED Displays

DS

(Device State)

DE

(Device Error)

Meaning
Long flashing

= 0.5 s on / 1 s off

Short flashing

= 0.25 s on / 1 s off

OFF

OFF

Technology unit not ready, no control voltage

ON

OFF

Technology unit ready, no error, at least one frequency inverter is communicating via the system bus

ON

Short flashing

Technology unit ready, however

One or more of the connected frequency inverters is in fault status

Long flashing

OFF

Technology unit ready and at least one further participant is connected to the system bus, but

No frequency inverter on the system bus (or connection interrupted)

Address error for one or more system bus participants

Long flashing

Short flashing

Flash interval

1 x - 1s pause

System bus is in status "Bus Warning"

Communication on system bus interrupted or

No other participant present on the system bus

Long flashing

Short flashing

Flash interval

2 x - 1s pause

System bus is in status "Bus off" or

The system bus 24V power supply was interrupted during operation

Long flashing

Short flashing

Flash interval

3 x - 1s pause

No system bus 24V power supply (system bus is in status "Bus off")

Long flashing

Short flashing

Flash interval

4 x - 1s pause

Module error

EEPROM error

Long flashing

Short flashing

Flash interval

5 x - 1s pause

Module error

AOUT error (analog output)

DIP switch configuration error

OFF

Short flashing

Flash interval

1…7 - 1s pause

System error, internal program sequence interrupted

EMC interference (observe wiring guidelines!)

Module faulty

IO channel

Display

Meaning

IO channel

Display

Meaning

DI 1

ON

High potential DIN1

DO 1

ON

High potential DOUT1

DI 2

ON

High potential DIN2

DO 2

ON

High potential DOUT2

DI 3

ON

High potential DIN3

DI 4

ON

High potential DIN4

DI 3/4, DO 1/2

Available according to the type of IO
module

Pos : 15 /T echnisc he I nf ormati onen/I O - Er weit er ung/F ehl er mel dungen [IO E Allgemei n] @ 2\ mod_1352389805965_388. doc x @ 50953 @ 6 @ 1

Error messages

Error messages for the module - the present or archived messages for the last error - can be read out
via the module parameter (P170) (see Parameterisation).

Error

Meaning

Comments

1000

EEPROM error

EMC fault, module defective

1030

System bus OFF

No 24 V supply to bus, connections not correct

2000

DIP switch changed

DIP switch configuration changed during operation

2001

DIP switch configuration incorrect

Invalid DIP switch settings

2010

Error at analog output

Overload, reference voltage, short-circuit, calibration error

2020

Inverter does not support the module

Incorrect inverter type connected