Led displays, Error messages, Io-extension – sk tu4-ioe-m12 – NORD Drivesystems TI 275281206 User Manual
Page 8

IO-Extension
– SK TU4-IOE-M12
8
TI 275281206 - 4912
LED Displays
DS
(Device State)
DE
(Device Error)
Meaning
Long flashing
= 0.5 s on / 1 s off
Short flashing
= 0.25 s on / 1 s off
OFF
OFF
Technology unit not ready, no control voltage
ON
OFF
Technology unit ready, no error, at least one frequency inverter is communicating via the system bus
ON
Short flashing
Technology unit ready, however
•
One or more of the connected frequency inverters is in fault status
Long flashing
OFF
Technology unit ready and at least one further participant is connected to the system bus, but
•
No frequency inverter on the system bus (or connection interrupted)
•
Address error for one or more system bus participants
Long flashing
Short flashing
Flash interval
1 x - 1s pause
System bus is in status "Bus Warning"
•
Communication on system bus interrupted or
•
No other participant present on the system bus
Long flashing
Short flashing
Flash interval
2 x - 1s pause
•
System bus is in status "Bus off" or
•
The system bus 24V power supply was interrupted during operation
Long flashing
Short flashing
Flash interval
3 x - 1s pause
•
No system bus 24V power supply (system bus is in status "Bus off")
Long flashing
Short flashing
Flash interval
4 x - 1s pause
Module error
•
EEPROM error
Long flashing
Short flashing
Flash interval
5 x - 1s pause
Module error
•
AOUT error (analog output)
•
DIP switch configuration error
OFF
Short flashing
Flash interval
1…7 - 1s pause
System error, internal program sequence interrupted
•
EMC interference (observe wiring guidelines!)
•
Module faulty
IO channel
Display
Meaning
IO channel
Display
Meaning
DI 1
ON
High potential DIN1
DO 1
ON
High potential DOUT1
DI 2
ON
High potential DIN2
DO 2
ON
High potential DOUT2
DI 3
ON
High potential DIN3
DI 4
ON
High potential DIN4
DI 3/4, DO 1/2
Available according to the type of IO
module
Pos : 15 /T echnisc he I nf ormati onen/I O - Er weit er ung/F ehl er mel dungen [IO E Allgemei n] @ 2\ mod_1352389805965_388. doc x @ 50953 @ 6 @ 1
Error messages
Error messages for the module - the present or archived messages for the last error - can be read out
via the module parameter (P170) (see Parameterisation).
Error
Meaning
Comments
1000
EEPROM error
EMC fault, module defective
1030
System bus OFF
No 24 V supply to bus, connections not correct
2000
DIP switch changed
DIP switch configuration changed during operation
2001
DIP switch configuration incorrect
Invalid DIP switch settings
2010
Error at analog output
Overload, reference voltage, short-circuit, calibration error
2020
Inverter does not support the module
Incorrect inverter type connected