Error messages, Parameters, Profinet io bus module – sk cu4-pnt – NORD Drivesystems TI 275271015 User Manual
Page 7

PROFINET IO Bus module – SK CU4-PNT
TI 275271015 - 4913
7 / 8
Error messages
Error messages from the module - present errors or archived messages relating to the last error - can
be read out via the module parameter (P170). The error messages are lost if the module is switched
off.
Error
Meaning
Remarks
100.0
EEPROM error
EMC fault, module defective
102.0
Timeout
via P151/P513 monitoring
103.0
System bus BUS OFF
No 24V supply to the bus, connections not correct
104.0
Module temperature too high
only SK CU4-…, permissible internal temperature of the bus
module exceeded for approx. 60 sec
560.0 …
560.9
Internal error
Module not ready
561.0
General network error
561.1
Ethernet Watchdog timeout
561.2
Bus cable fault
Bus cable connection interrupted
561.3
IP address error
IP address of the module has been doubly assigned
563.0
Firmware version incompatible
The firmware version cannot be used for the device
564.0
MAC address error
Errors which occur in relation to the module are depicted as follows in the error memory of the
frequency inverter (P700 / P701).
Error
(E010)
Meaning
Remarks
10.0
Connection error
Contact to SK xU4 lost
10.1
ASIC errors
Communication to Ethernet - ASIC lost
•
Switch-off of the supply voltage
•
Reduce the temperature of the module (only SK CU4-…)
10.2
Ethernet Watchdog timeout
Telegram transfer error
•
Check the connections and links, program sequence and
Bus Master
10.3
Timeout by P151/P513
Telegram transfer error
•
Check the connections and links
•
Check the Watchdog time
10.4
IP address error
IP address of the module has been doubly assigned
10.5
Internal error
Module not ready for operation, configuration error
10.6
Bus cable fault
Bus cable connection interrupted
10.8
The connection between the inverter
and the module had a timeout
Only SK TU3 module
10.9
Module missing (P120)
Only SK xU4 module
Pos : 27 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ Allgemei n - Syst emübergreifend/ Par ameter [SK xU x-. .. Allgemei n - Fr equenzumric ht er] @ 4\ mod_1384953855694_388.doc x @ 105781 @ 5 @ 1
Parameters
Frequency inverter: The following frequency inverter parameters must be adapted for setting up
communication between the frequency inverter and the bus module (for details see frequency
converter manual).
Parameter [-Array]
Meaning
Remarks
P120 [-01]
Option monitoring
"Auto“ (default setting)
Only SK xU4
P509
Control word source
SK TU3-… on SK 5xxE: "Ethernet TU”
SK xU4-… on SK 180/SK 2xxE: "System bus"
P510 [-01 … -02]
Setpoint source
"Auto“ (default setting)
P513
Time-out
Monitoring of the SK TU3 bus module
Only SK 5xxE
P543 [-01 …-03 (-05)]
and P543 … P545
Bus actual values (1 …3 (… 5))
Possible settings according to (P418)
P546 [-01 …-03 (-05)]
and P546 … P548
Bus target values (1 …3 (… 5))
Possible settings according to (P400)
P700 [-01] / P701
Current / last failures
Information parameters
P740 / P741
Process data bus In / Out
Information parameters
P745
Module version
Information parameters
Only SK TU3
P745
Module status
Information parameters
Only SK TU3
P748
CANopen / System bus status
Information parameters
Pos : 28 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /Paramet er [ PNT Allgemei n] @ 4\ mod_1385367612358_388. doc x @ 106326 @ @ 1