Configuration, Led indicators, Profinet io bus module – sk cu4-pnt – NORD Drivesystems TI 275271015 User Manual
Page 5: Profinet-specific led

PROFINET IO Bus module – SK CU4-PNT
TI 275271015 - 4913
5 / 8
Configuration
Configuration of the module for remote maintenance or for the system bus is carried out via the DIP
switches. The DIP - switch settings are read after a "Power On" of the module.
DIP switch
Meaning
12
11
10
9
8
7
6
5
4
3
2
1
X
X
X
No function
X
0
System bus terminating resistor not set
1
System bus terminating resistor set
Access rights for remote maintenance
0
Only read access to parameters possible.
1
Read and write access to parameters possible.
0
No control possible.
1
Control is possible.
0
TCP/IP open connection.
1
Secure TCP/IP connection.
1. System bus (DIP 1)
The system bus must be terminated at both physical
ends.
2. (DIP 2 - 9)
No function
3. Access rights for remote maintenance (DIP 10 – 12)
Via the Ethernet protocols TCP and UDP the module
and the connected frequency inverter can be
accessed using remote maintenance. The type of
access is determined via the DIP - switch with inputs
10 to 12.
Pos : 21 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /LED Anzeigen [SK CU 4-PNT] @ 4\ mod_1385046539436_388. doc x @ 106074 @ 5 @ 1
LED indicators
The operating statuses of the module are visualised using LED indicators.
No.
Name
Colour
Meaning
1
RUN
green
Ethernet State
BF
red
Ethernet Error
2
L1
green
Link 1
A1
yellow
Activity 1
3
L2
green
Link 2
A2
yellow
Activity 2
Pos : 24 /T echnisc he I nf ormati onen/ SK xU x - Bus - Erweit erungen/ PROF INET IO /LED Anzeigen- PROF INET spezifisc he LED [PN T Allgemein] @ 4\ mod_1385130089638_388.doc x @ 106275 @ @ 1
PROFINET-specific LED
RUN
(Ethernet State)
Meaning
BF
(Ethernet Error)
Meaning
OFF
No operating voltage
Initialisation
OFF
No error
Flashing green
No connection to PROFINET IO controller
No parameter communication
No process data communication
Flashing red
No process data communication
à e.g. wrong GSDML file
Green ON
Parameter communication active
Process data communication active
Red ON
Ethernet error
à there is no physical
connection to a further participant
Double-flashing
red
(2 x 0.25 s,+
1sec pause)
PROFINET or FI timeout,
(see also P151, P513)
1
…
12
ON
OF
F