Error messages, Parameterisation, Further documentation and software (www.nord.com) – NORD Drivesystems TI 275271006 User Manual
Page 5
IO-Extension
– SK CU4-IOE
TI 275271006 - 4912
5
Error messages
Error messages for the module - the present or archived messages for the last error - can be read out
via the module parameter (P170) (see Parameterisation).
Error
Meaning
Comments
1000
EEPROM error
EMC fault, module defective
1030
System bus OFF
No 24 V supply to bus, connections not correct
2000
DIP switch changed
DIP switch configuration changed during operation
2001
DIP switch configuration incorrect
Invalid DIP switch settings
2010
Error at analog output
Overload, reference voltage, short-circuit, calibration error
2020
Inverter does not support the module
Incorrect inverter type connected
Pos : 16 /T echnisc he I nf ormati onen/I O - Er weit er ung/ Par ametrierung [I O E Allgemein] @ 2\ mod_1352389903587_388.doc x @ 50978 @ 6 @ 1
Parameterisation
Inverter: In order to establish communication between the inverter and the IOE module, the following
inverter parameters must be changed.
Parameter
Meaning
Comments
(P514)
Bus speed
5 (= 250 kBaud)
(P515 [-01])
Bus address
FI 1 = 32
FI 2 = 34
FI 3 = 36
FI 4 = 38
(P480 [-
01 …-08])
DIN function of the device
Possible settings according to (P420)
(P481 [-
05 …-08])
DOUT function of the device
Possible settings according to (P434)
(P400 [-
03 …-06])
AIN function of the device
Possible settings according to (P400)
(P418 [-
02 …-03])
AUT function of the device
Possible settings according to (P418
IO extension: The module provides a selection of parameters for setting or displaying special
operating values. The parameters can be changed with the aid of the NORDCON software or with a
ParameterBox. Communication is only possible via an SK 54xE or SK 2xxE which is connected to the
module.
Parameter
Meaning
Comments
(P150)
Set relays
Set DOUT directly or control via BUS
(P152)
Factory setting
Reset the module parameters, calibrate AOUT
(P153 [-
01 …-02])
Minimum system bus cycle
Reduction of bus load due to the module
(P160)
Set analog output
Set AOUT directly or control via BUS
(P161 [-
01 …-09])
Filter time
Debounce or round input signals
(P162)
Send broadcast
Activate Broadcast mode (control of several
inverters by this module)
(P163)
Invert analog output
Invert analog signal
(P170 [-
01 … 02])
Present errors
Display of module errors
(P171 [-
01 … 03])
Software version
Firmware version / Revision
(P172)
Configuration
Module type
(P173)
Module status
Status of system bus or connected FI
(P174)
Status of digital inputs
Display of DIN switching status
(P175)
Relay status
Display of DOUT switching status
(P176 [-
01 … 03])
Actual voltage
Voltage level of analog signals
Pos : 17 /T echnisc he I nf ormati onen/I O - Er weit er ung/ Weiterf ührende D okument ati onen und Soft ware [I OE Allgemein] @ 2\ mod_1352390057120_388. doc x @ 51003 @ 6 @ 1
Further documentation and softwar
Document
Name
Document
Meaning
NORD CON
Parameterisation and diagnostic software
BU 0200
SK 2xxE frequency inverter manual
BU 0000
Description of NORD CON software
BU 0500
SK 5xxE frequency inverter manual
BU 0040
ParameterBox manual