Installation, Connections, Connection examples – NORD Drivesystems TI 275271006 User Manual
Page 2
IO-Extension
– SK CU4-IOE
2
TI 275271006 - 4912
Installation
Installation location
Inside the connection unit of a frequency inverter (SK 2xxE)
Fastening
With screw fasteners
Pos : 9 /T ec hnis che Inf or mationen/ IO - Er weiter ung/Ansc hlüss e [SK CU 4-IO E] @ 2\ mod_1353314893934_388. doc x @ 51226 @ 6 @ 1
Connections
Terminals
Screw terminals
1 terminal bar, with 16 connections, (5 mm spacing)
Cable cross section
0,14 … 2,5 mm
AWG 14-26
PE connection
Via inverter
Via screws if installed in inverter
Schematic circuit diagram of electrical connection
(Terminal designations in example: Frequency inverter SK 2xxE)
SK CU4-IOE
SK 2xxE
VI 24V
GND/0V
SYS +
SYS -
24V
GND/0V
SYS +
SYS -
Level
Contact
Designation
Description
S
yste
m
b
u
s le
ve
l,
d
igita
l sig
n
a
ls
44
VI 24V
Supply voltage (+24 V - in)***
40
GND/0V
Reference potential (0 V / GND)***
C1
DIN1
Digital input 1
C2
DIN2
Digital input 2
77
SYS+
System bus data cable +**
78
SYS-
System bus data cable -**
40
GND/0V
Reference potential (0 V / GND)
A
n
a
lo
g
sig
n
a
ls
11
VO 10V
10 V Reference voltage
14
AIN1+
Analog input 1, positive
13
AIN1-
Analog input 1, negative
12
AGND/0V
Analog Ground (internally connected to terminal 40)*
17
AOUT
Analog Out
11
VO 10V
10 V Reference voltage
16
AIN2+
Analog input 2, positive
15
AIN2-
Analog input 2, negative
12
AGND/0V
Analog Ground (internally connected to terminal 40)*
* AGND/0V is internally connected to the reference voltage of the module GND/0V via a special
component. In order to prevent damage to the module or faults in the analog signals, the two
contacts must not be bridged
** Use system bus cable kit (included in scope of delivery), black = SYS -, grey = SYS +
*** Use 24VDC cable kit (included in scope of delivery), brown = 24V, blue = GND/0V
Pos : 12 /T echnisc he I nf ormati onen/I O - Er weit er ung/ Ans chl uss beis piel e [IO E Allgemei n] @ 2\ mod_1352736753713_388. doc x @ 51105 @ 6 @ 1
Connection examples
The following connection examples are generally applicable for NORD IO modules. The number or
type of the available IOs and their configuration on the terminal rail varies according to the module.
The actual availability or the designation of the individual contacts should be obtained by reference to
the description of the connections. The technical data (e.g. load capacity) must be taken into account.