Configuration, Broadcast mode – NORD Drivesystems TI 275271006 User Manual
Page 3
IO-Extension
– SK CU4-IOE
TI 275271006 - 4912
3
Digital signals
Control
voltage
source
Digital input
Digital output
External
supply
GND/0V
VI 24V
DIN
DIN
GND2/0V2
DOUT
VI 24V2
GND2/0V2
VI 24V
DOUT
VI 24V2
GND/0V
Internal supply
GND/0V
VO 24V
DIN
DIN
GND2/0V2
VO 24V
DOUT
VI 24V2
GND/0V
Analog signals
Signal type*
Analog / Differential input
Analog output
0/2 … 10 V
0/4 … 20 mA
-
10 … 10 V**
VO 10V
AGND/0V
AIN -
AIN +
AGND/0V
AOUT
Potentiometer
(10
kΩ)
0 … 10 V
VO 10V
AGND/0V
AIN -
AIN +
R=10kΩ
* The relevant IOs must be configured via DIP switches according to the form of the signal
** Analog input only
Pos : 13 /T echnisc he I nf ormati onen/I O - Er weit er ung/ Konfigur ati on [I OE Allgemein] @ 2\ mod_1352388400441_388. doc x @ 50928 @ 6 @ 1
Configuration
Configuration of the module is mainly performed via the DIP switches. The DIP switches are read after
a "power on" of the module. A change to the DIP switch during operation has no effect.
The system bus must be terminated at both of its physical ends (if necessary set the "System bus
termination resistor" DIP switch).
Note
Broadcast mode
In "Broadcast mode, which is activated via the parameter (P162), the module can access up to 4 inverters in
parallel. Therefore the frequency inverters jointly access the I/Os and evaluate the input signals according to their
own parameterisation. Output signals from the frequency inverters which are sent to the common IO module are
linked by a logical "OR" within the module. i.e. a digital output is set as soon as one of the four frequency inverters
addresses it. In addition, the highest analog value is provided via the analog output of the IO extension.