SPECIFICATIONS
Input Signal:
4-20 mA DC.
Input Impedance: 460 Ohm max @ 20 mA DC.
Material: Aluminum diecasting.
Air Supply: 20 to 100 psi (1.4 to 6.9 bar).
Air Connection: 1/4˝ NPT.
Gage Connection: 1/8˝ NPT.
Conduit Connection: 1/2˝ NPT.
Linearity: ±0.5% of full scale.
Hysteresis: ±0.5% of full scale.
Sensitivity: ±0.2% of full scale.
Repeatability: ±0.3% of full scale.
Air Consumption: below 0.07 scfm (2 LPM) at 20 psig (1.4 bar)
supply.
Flow Capacity: 2.5 scfm (70 LPM) at 20 psig (1.4 bar) supply.
Stroke: 0 to 90°.
Enclosure Rating: NEMA 4X (IP66).
Ambient Temperature: Operating: -40 to 185°F (-40 to 85°C).
Weight: 3.3 lb (1.5 kg).
Lever: 175: 0.39 to 1.57˝ (10 to 40 mm); 275: NAMUR.

Series 275 PRECISOR

®

III Electro-Pneumatic Positioner controls

valve stroke accurately using an input signal of 4 to 20 mA from the
controller. In addition, a highly efficient microprocessing operator built
into the product. Performs various powerful functions such as Auto
calibration, PID control, Alarm and Hart

®

protocol.

FEATURES
• LCD allows user to directly check the positioner condition in the field.
• Endures severe vibration.
• Operates normally regardless of changes in supply pressure during

operation.

• Simple to use auto calibration.
• Easily equipped on small actuators because of its small size.
• Low air consumption reduces operating cost.
• Can be used in low voltage (8.5V), leaving no limitation in controller.
• Variable orifice is applied in case of a small actuator, the hunting is

controlled to the optimum condition during operation.

• HART

®

communication available for configurating parameters or

monitoring the valve position.

• Analog feedback signal (4 to 20 mA).
• The adjustment of valve characteristics available.
• Specific flow control is available with setting 16 points at users’

command.

• Tight Shut-Close and Shut-Open can be set in the programming

menu.

• PID parameters can easily be adjusted in the field without additional

communicator.

• Split ranges such as 4-12 mA, 12-20 mA are available.
• The positioner can manually actuate the valve or damper.

6-13/64

[157.56]

3-17/32

[89.69]

21/64
[8.33]

5-11/32

[135.73]

CONDUIT 1/2˝

NPT 1/4˝
SUPPLY

6-7/64

[155.18]

31/64

[12/30]

3/8

[9.53]

13/64
[5.16]

1-25/32

[45.24]

2-11/32

[59.53]

1-25/32

[45.24]

1-21/32

[42.07]

1-25/32

[45.24]

2-49/64

[70.25]

NPT 1/4˝

OUT 2

NPT 1/4˝

OUT 1

2-3/8

[60.33]

MOUNTING BRACKETS

6-31/64

[164.70]

3-35/64

[90.09]

6-17/32

[165.89]

3-35/64

[90.09]

4-5/64

[103.58]

4-5/8

[117.48]

Series 275 PRECISOR

®

III Electro-Pneumatic Positioner

Specifications - Installation and Operating Instructions

Bulletin F-98

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

HART

®