Protective devices in it systems – American Power Conversion SYMF800KH User Manual

Page 46

background image

Appendix: IT Systems

40

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

In installations where the neutral is distributed, the following conditions must be fulfilled:

In the condition:

Protective devices in IT systems

The following protective devices are recognized in IT systems:

• Insulation monitoring devices

• Overcurrent protective devices

• Residual current protective devices

The following diagram shows a Symmetra

®

MW installed in a IT system:

• Earthing arrangements and protective conductors - Symmetra

®

MW in “IT installation”

is the nominal A

C

RMS voltage between phase and neutral

is the impedance of the fault loop comprising the phase conductor and the protective conductor of
the circuit

is the impedance of the fault loop comprising the neutral conductor and the protective conductor of
the circuit

is the operating current of the protective device. The disconnecting time is 5 seconds (distribution
circuits)

Z

s

U

0

2 I

a

×

-------------

U

0

Z

s

Z

s

I

a