Electrical specifications, Ac input – American Power Conversion SYMF800KH User Manual
Page 34
28
Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D
Electrical Specifications
AC Input
WARNING!
Supply the UPS from a dedicated, 3 × 400/230 V, L1, L2, L3, N, PE source or a
high-impedance grounded system.
CAUTION!
Ensure clockwise phase rotation (L1, L2, L3) of input voltages.
CAUTION!
AC and DC disconnect switches and over-current protection must be included in the
installation.
Note
All wiring must comply with all applicable national and/or local electrical codes.
Note
Max. prospective RMS short-circuit current on input terminals: 200 kA
Max. prospective RMS short-circuit current on DC terminals: 50 kA
AC Input
Input rating
800 kW/kVA
Power Factor
1
Input Voltage
380 V
Input Frequency
50 Hz
Nominal input current (note 1)
1132 A
Input Current Limitation (note 2)
1422 A
Input Voltage
400 V
Input Frequency
50 Hz
Nominal input current (note 1)
1203 A
Input Current Limitation (note 2)
1466 A
Input Voltage
415 V
Input Frequency
50 Hz
Nominal input current (note 1)
1159 A
Input Current Limitation (note 2)
1447 A