beautypg.com

Dc input, Ac output, Ac input external bypass ssw – American Power Conversion SYMF800KH User Manual

Page 35: Heat dissipation

background image

Specifications: Electrical Specifications

Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D

29

DC Input

AC Output

AC Input External Bypass SSW

The External Bypass SSW is designed to accommodate a continuous overload of 25%.

Heat dissipation

24.74 kW / 84.4 kBTU/hr (note 6)

DC Input

Nominal Voltage (note 3)

2 x 384 V

I

Nom

Discharge (note 4)

1085 A

I

Max

Discharge (note 5)

1276 A

CAUTION!
The minimum DC voltage rating of the battery supply over-current protective device is
500 V.

AC Output

Voltage

380 V

- Current Nom (note 8)

1094 A

- Max (note 7)

1311 A

Voltage

400 V

- Current Nom

1155 A

- Max (note 7)

1444 A

Voltage

415 V

- Current Nom

1113 A

- Max (note 7)

1391 A

AC Input External Bypass SSW

External Bypass SSW Max Input Current (100% load)

380 V

1094 A

400 V

1155 A

415 V

1113 A