Required breaker settings (400 v systems), Input and upstream breakers — minimum settings, Output and downstream breakers -— minimum settings – American Power Conversion SYMF800KH User Manual
Page 37
![background image](/manuals/37202/37/background.png)
Symmetra MW 800 kW 3 × 400/230 V Installation - 990-1510D
31
Required Breaker Settings (400 V Systems)
The Symmetra® MW is a fault-tolerant system capable of handling and surviving overloads and
internal/external faults. The overload performances and fault clearings are possible when the system
meets specified minimum requirements for breaker settings. The settings are specified in the tables
below, but some of them can also be found in the Electrical Specification section. The settings are all
minimum settings and may not result in a drop-out.
Input and upstream breakers — minimum settings
Output and downstream breakers -— minimum settings
Note
Contact APC Application Team for Required Breaker Settings in 380 V and 415 V
systems.
See also
See separate guide on parallel operation for information on required breaker settings in
parallel systems.
Q1, Q5, and any upstream breaker
Duration [S]
Current [A]
Total load [%]
Event/Operation
< 0.005
22 kA
--
Internal fault clearing
1466*
127
Overload on-line
1195
100
On-line
1315
110
On-line+ Max. Battery
charge
* Only applicable to Q1
∞
∞
∞
Q2, Q4, Q6, and any downstream breaker
Duration [S]
Current [A]
Total load [%]
Event/Operation
< 0.005
22 kA
--
Internal fault clearing.
60
2406*
200
Overload on-line
600
1504*
125
Overload on-line
1155
100
On-line
* Only applciable to Q2 and Q4
∞