Dual Output Control:
OFF
PV
Set point
ON
Heating
Dead band
Heating hysteresis
Figure 4.
of dual loop output
ON-OFF control
Cooling hysteresis
Cooling
PV
0
Dead band:dead
band width:positive
Dead band:dead
band width:negative
PV
0
Output
Heating
Cooling
Set Point
Output
Heating
Cooling
Set Point
Figure 5: PID control,
Dead band is positive
Figure 6: PID control,
Dead band is negative
Description of Function and Parameters Setting:
PID program controlled by 8 patterns (Pattern No. 0 ~ 7) is supported in SCD series. Each pattern contains 8
steps (step No. 0 ~ 7), 1 Link Pattern parameter, 1 Cycle parameter and 1 Actual Step parameter
Start Pattern:
is in operation mode and is used to set the Start Pattern of PID program control (This
parameter appears in
mode only).
Steps: Including set point X and execution time T, the two parameters setting. The set point (SV) should reach
temperature X after the period of execution time T. If the set point is the same as the result of the previous
setting, it is called “Soak” program control. If not, it is called “Ramp” program control. Therefore, PID program
control is also called Ramp/Soak program control.
The default of step No. 0 in this controller is Soak program control. The controller will control the temperature
(PV) and reach the set point X and keep the temperature at set point X. The period of execution time is time T
provided by step No. 0.
Link Pattern Parameter: For example, when
is set as 2, it indicates that pattern No. 2 will be the next to
be executed after the execution of pattern No. 0. If it is set to
, the program will stop after the current pattern
has been executed and the temperature will keep at the set point for the last step.
Cycle Parameter: Additional execution cycle number. For example, when
is set as 2, pattern No. 4
should be executed twice. Including the original one time of execution, the total execution will be three times.
Actual Step Parameter : Number of steps being executed per pattern (can be set as 0 ~ 7). For example, when
is set as 2, pattern No 7 will not execute other steps but step 0 to step2.
Execution: When
is set as
, the program will start to execute in order from step 0 of start pattern.
When
is set as
, the program will stop and the control output will be disabled.
When
is set as
, the program will stop and the temperature at that time will be controlled at the set
point before the program stops. Select
again, and the program will restart and execute from step 0 of start
pattern.
When
is set as
, the program will hold and the temperature at that time will be controlled at the set
point before the program holds. Select
again, and the program will follow the step before hold and start to
execute throughout the rest of the time.
Retransmission Output:
When the 1
st
group output of this controller is linear voltage or current output, it can be Retransmission that is the
output variation corresponding with input. For example, when read value=0 with input range 0~1000, output will
be 0mA or 0V. When read value=1000, output will be 20mA or 10V.