TROubLESHOOTInG

problem

probable cause

Try...

Display blank

No power to the unit

Check for minimum 12 VDC at power

terminals

Short in sensor circuit

Disconnect sensor, see if display returns

(zero flow rate)

Display missing segments

Damaged display module

Contact Dwyer Instruments, Inc. for replacement

Display reading meaningless

Unit’s microcontroller crashed

Disconnect and reconnect power, if problem

characters

repeats, contact distributor for

return/replacement

Display reads normally,

Wrong K-factor or time base entered

Enter correct K-factor from meter, fitting, or

flow rate incorrect

manual

Display reads normally,

Wrong pulse output setting

Use “Set P” to correct pulse output setting

incorrect pulse output

Polarity reversed on pulse output terminals

Reverse leads

Display reads normally, but

Wrong 20 mA setting

Use “Set 20” to correct target top flow rate

no (or incorrect) 4 to 20 mA output

Inadequate loop power supply voltage

Check voltage (For 4 to 20 mA applications,

24 VDC recommended)

Polarity incorrect in 4 to 20 mA loop circuit

Compare to Connections diagram

Display reads zero when

Flow sensor failed

Consult flow sensor manual for how to test

there is flow

Break in flow sensor circuit

Check for continuity with multimeter

Display reads flow rate when

Long flow sensor wire, running parallel to

Reroute wire or change to shielded wire

there is none

power wires

Flow sensor malfunction

See flow sensor manual to check