TAbLE Of cOnTEnTS

General Information

General Information, Features, Specifications ....................................................................................................page 1

Installation

Wall Mount, Meter Mount, Panel Mount .............................................................................................................page 2

Connections, RTI (Option -DRO), -DRO Relay Board Specifications ...................................................................page 3

connection Diagrams

RTI, RTI-W-VPS .......................................................................................................................................................page 4

RTI-X-DRO, RTI/EFS2 or IEFS Magmeter .............................................................................................................page 5

RTI/EFS2 or IEFS Magmeter/Dual Power Supply ...............................................................................................page 6

(Quick) Settings

Quick Settings Overview .......................................................................................................................................page 7

Settings

K-Factor, Reading in Other Units ..........................................................................................................................page 8

Set K, Set P/Flow Alarm, Set 20 mA, Set Decimal Point, Set Time Unit ...........................................................page 8

Operation

Resettable Totalizer; 4 to 20 mA Output, Pulse Output ......................................................................................page 9

Troubleshooting

Problems, Probable Causes, to Try ................................................................................................................back page

TAbLES AnD DIAGRAMS

Features, Specifications .......................................................................................................................................page 1

Meter Mount, Panel Mount ..................................................................................................................................page 2

Dual Relay Board Specifications ..........................................................................................................................page 3

Connections: RTI, RTI-W-VPS ................................................................................................................................page 4

Connections: RTI-X-DRO, RTI/EFS2 or IEFS Magmeter .......................................................................................page 5

Connections: RTI/EFS2 or IEFS Magmeter/Dual Power Supply ........................................................................page 6

Quick Settings Overview .......................................................................................................................................page 7

K-Factor ..................................................................................................................................................................page 8

Resettable Totalizer ..............................................................................................................................................page 9

Troubleshooting Problems, Probable Causes, to Try .....................................................................................back page

page 1

GEnERAL InfORMATIOn

The Series RTI flow displays are microcontroller-based indi-

cator/transmitters that show flow rate and total and provide

output signals. The RTI is powered by external DC voltage and

has both pulse and 4 to 20 mA analog outputs. When the RTI

is being used in the 4 to 20 mA mode, it is a “two-wire” or

“loop-powered” device, meaning that the 4 to 20 mA output

signal doubles as its power supply.

The addition of a dual-relay output board allows for certain

applications requiring contact output isolation (e.g., certain

metering pumps and water treatment controls). Dual solid

state relays provide exactly the same pulse output as the

standard unit, and each can signal one external device. A

non-resettable total is also available. The RTI can be ordered

in a plastic enclosure with a 115 VAC power supply for use

with mechanical meters, or with a built-in 115 VAC/12 to 24

VDC dual power supply for magmeters.

The RTI can be factory-mounted on the meter (-M) or remotely

wall mounted with the brackets provided (-W). The RTI is also

available as a panel mount (-P) with an open back for easy

installation in the user’s own electrical enclosure. Most RTI’s

can be converted from wall-to-meter or meter-to-wall mount

configurations after installation if needed.

Housings for the -W and -M models are rugged cast aluminum,

potted and gasketed for maximum environmental protection.

A membrane keypad allows settings to be changed without

removing the cover. (Password protection, a standard feature,

can be used to prevent settings from being changed.)

**Includes password protection for tamper prevention

when needed

Lower Housing

Setup Keys**
Cover Screws

Electronics Module

Wall-Mount Brackets

Strain Relief

Display

fEATuRES

**Includes password protection for

tamper prevention when needed

SpEcIfIcATIOnS*

power

Display

Rate

Total

Outputs current Sinking pulse

Analog

pulse Output Range

Input

Input Range

K-factor Range

flow Alarm Output Range

Operating Temperature

Environmental

RTI

*Specifications subject to change

12 to 30 VDC, 4mA (4 to 20 mA when loop-powered)

6-digit autorange, 1/2" character height

8-digit, 5/16" character height
Scaled Pulse output (0.1 sec duration 6.1 Hz max), or (High Alarm output or Low Alarm output)
Sensor pass-through Pulse output (unscaled)

4 to 20 mA loop; 24 to 30 Vdc

0.1 - 9999999.9 units/pulse

5V pulse or contact closure

1.0 - 1,500 pulses/second

.001 - 99999.999

.01 - 999999.99

-30 to 65˚ C (-22 to 148˚ F)

NEMA 4X, IP66