1.3 Start up
When unit is powered up the following sequence of events occur:
1. The 12V DC power is applied to the airflow sensor and the alarm then performs a self test
on the functions, LEDs and audible alarm (approx 2 sec) and then initiates a delay timer to
allow the airflow sensor to stabilize.
2. During the whole of the delay period all alarms and relay outputs are inhibited and the Red &
Green LEDs will be permanently ON.
3. At the end of the delay period the unit performs one of two options:
a. If the alarm calibration has been previously completed - the unit goes to normal
operating mode (Run).
b. If the unit has not been calibrated - the Red & Green LEDs will flash on/off and the
audible alarm will be muted. It is then possible to press the Enter button for 5 secs
and go into the calibration mode – (See ‘Quick Start Installation’ below for details of
the Calibration procedures).
AV-670:B-32 10/1/09 2:20 PM Page 11
- 166T (1 page)
- 160S (2 pages)
- PAFS-1000 (1 page)
- 160F (2 pages)
- Mark II WSI (4 pages)
- MW-1 (2 pages)
- 89088 (12 pages)
- 660 (2 pages)
- FLST (4 pages)
- AFG (6 pages)
- FAFM (2 pages)
- DAFM (2 pages)
- STRA (4 pages)
- 530 (2 pages)
- AVFS (2 pages)
- 641RM (4 pages)
- 641B (4 pages)
- 641 (4 pages)
- VTT (2 pages)
- SFI-700 (2 pages)
- GFM (32 pages)
- GFC (40 pages)
- DMF (44 pages)
- GFM2 (20 pages)
- GFM3 (22 pages)
- TFP-LI (30 pages)
- TFP-GI (27 pages)
- TBS (7 pages)
- HFT (4 pages)
- CAM (6 pages)
- PWD (3 pages)
- BAT (3 pages)
- FPCA (4 pages)
- FPCA (2 pages)
- SPK (4 pages)
- MFS (8 pages)
- LOFM (3 pages)
- FLMG (12 pages)
- MFS2 (16 pages)
- PFT (4 pages)
- IPFS (7 pages)
- UFB (48 pages)
- UFC (56 pages)
- Series PUB (44 pages)