ZERO

and

SPAN

(Calibration of Zero and Span) SUB MENUS

The lower display reads

CAL

in this mode.

ZERO

Calibration

NOTE: For accurate calibration, DO NOT apply any pressure when performing
this function.

With the display reading

ZERO

, press the ENTER key. The upper display will blink.

Press ENTER again to complete the zeroing of the instrument or press the

MENU

key to cancel.

SPAN

Calibration

With the display set to

SPAN

, apply full scale pressure to the unit. Press the ENTER

key. The upper display will blink. Press ENTER again to complete the calibration or
press the

MENU

key to cancel.

Maintenance
Upon final installation of the Series ISDP intrinsically Safe Differential Pressure
Transmitter, no routine maintenance is required. The Series ISDP is not field serviceable
and should not be returned if repair is needed (field repair should not be attempted and
may void warranty). Be sure to include a brief description of the problem plus any rele-
vant application notes. Contact customer service to receive a return goods authorization
number before shipping.