These SUB MENUS become accessible if the instrument is set for flow. When measuring
flow, the area of the duct must be specified. Tables 3 and 4 show the input range vs max-
imum flow and duct size. For a rectangular duct the maximum size is specified in square
feet or meters. For a circular duct the maximum size is specified as the diameter. X, Y and
circular dimensions are entered in feet with 0.01 foot resolution for FLOr = LO and 0.1 foot
resolution for FLOr = HI, or entered in millimeters with 1 millimeter resolution.
ArEA
- Area, select
CIR
for a circular duct or
RECT
for a rectangular duct. If a
circular duct is selected, the
DIA
SUB MENU will be activated. If a rectangular duct is
selected, the
XDIM
and
YDIM
SUB MENUS will be activated.
DIA
- Diameter, enter the diameter of a duct
XDIM
- Enter the “X” dimension of a duct
YDIM
- Enter the “Y” dimension of a duct
d.S
(Display) MAIN MENU
PEAK
- Peak value
rESO
- Resolution
VALy
- Valley value
Pd.S
- Process display
ZERO
- Zero
DAMP
- Dampening level
PEAK
(Peak) SUB MENU
The Peak feature stores the highest pressure reading the instrument has measured
since the last reset or power up. At power up
PEAK
is reset to the present
pressure reading. To manually reset the
PEAK
value, press the ENTER key while in
the
PEAK
SUB MENU.
VALy
(Valley) SUB MENU
The valley feature stores the lowest pressure reading the instrument has measured
since the last reset or power up. At power up
VALy
is reset to the present
pressure reading. To manually reset the
VALy
value, press the ENTER key while in
the
VALy
SUB MENU.