Badger Meter 380 Series Btu System User Manual
Page 10
Page 10
7-11
Series 380 Impeller Btu System
Series 380 BACnet Object Map
Description
ID
Name
Units
Analog Input
AN1
TempIn
ºC, ºF
Analog Input
AN2
TempOut
ºC, ºF
Analog Value
AV1
VolFlow
gpm, gph, lpm, lps, lph,
ft
3
/s, ft
3
/m, ft
3
/h, m
3
/s,
m
3
/min, m
3
/h, custom
Analog Value
AV2
EnergyFlow
kBtu/min, kBtu/h, kW,
MW, HP, Tons, custom
Analog Value
AV3
TotalVol
gallons, galx100,
galx1000, liters, ft
3
, m
3
,
custom
Analog Value
AV4
TotEnergy
Btu, kBtu, MBtu, kWh,
MWh, kJ, MJ, custom
Analog Value
AV5
TempMode
dimensionless
Analog Value
AV6
FFilterCoef
dimensionless
Analog Value
AV7
TFiltCoef
dimensionless
Analog Value
AV8
SpHtCapac
Btu/lb-F
Analog Value
AV9
Density
lb/gallon
Analog Value
AV10
SerialNum
dimensionless
BACnet Protocol Implementation Conformance Statement
BMA Doc. x – 00x
Page 1 of 1
BACnet Standardized Device Profile
Device Profile
Tested
BACnet Smart Actuator (B-SA)
�
Supported BIBBs
Supported BIBBs
BIBB Name
Tested
DS-RP-B
ReadProperty - B
�
DS-WP-B
WriteProperty - B
�
DM-DDB-B
Dynamic Device Binding - B (Who-Is, I-Am)
�
Standard Object Types Supported
Object Type
Creatable
Deletable
Tested
Analog Input
No
No
�
Analog Value
No
No
�
Device
No
No
�
Data Link Layer Options
Data Link
Options
Tested
MS/TP Slave
baud rates: 9600, 19200,
38400, 76800 bps
�
Segmentation Capability
Segmentation Type
Supported
Window Size
(MS/TP product limited to 1)
Tested
Able to transmit segmented messages
No
N/A
Device Address Binding
Static Binding Supported
Tested
No
N/A
Character Sets
Character Sets supported
Tested
ANSI X3.4
�
Figure 6: BACnet Device Profile