beautypg.com

Badger Meter 380 Series Btu System User Manual

Page 10

background image

Page 10

7-11

Series 380 Impeller Btu System

Series 380 BACnet Object Map

Description

ID

Name

Units

Analog Input

AN1

TempIn

ºC, ºF

Analog Input

AN2

TempOut

ºC, ºF

Analog Value

AV1

VolFlow

gpm, gph, lpm, lps, lph,

ft

3

/s, ft

3

/m, ft

3

/h, m

3

/s,

m

3

/min, m

3

/h, custom

Analog Value

AV2

EnergyFlow

kBtu/min, kBtu/h, kW,

MW, HP, Tons, custom

Analog Value

AV3

TotalVol

gallons, galx100,

galx1000, liters, ft

3

, m

3

,

custom

Analog Value

AV4

TotEnergy

Btu, kBtu, MBtu, kWh,

MWh, kJ, MJ, custom

Analog Value

AV5

TempMode

dimensionless

Analog Value

AV6

FFilterCoef

dimensionless

Analog Value

AV7

TFiltCoef

dimensionless

Analog Value

AV8

SpHtCapac

Btu/lb-F

Analog Value

AV9

Density

lb/gallon

Analog Value

AV10

SerialNum

dimensionless

BACnet Protocol Implementation Conformance Statement

BMA Doc. x – 00x

Page 1 of 1

BACnet Standardized Device Profile

Device Profile

Tested

BACnet Smart Actuator (B-SA)

Supported BIBBs

Supported BIBBs

BIBB Name

Tested

DS-RP-B

ReadProperty - B

DS-WP-B

WriteProperty - B

DM-DDB-B

Dynamic Device Binding - B (Who-Is, I-Am)

Standard Object Types Supported

Object Type

Creatable

Deletable

Tested

Analog Input

No

No

Analog Value

No

No

Device

No

No

Data Link Layer Options

Data Link

Options

Tested

MS/TP Slave

baud rates: 9600, 19200,

38400, 76800 bps

Segmentation Capability

Segmentation Type

Supported

Window Size

(MS/TP product limited to 1)

Tested

Able to transmit segmented messages

No

N/A

Device Address Binding

Static Binding Supported

Tested

No

N/A

Character Sets

Character Sets supported

Tested

ANSI X3.4

Figure 6: BACnet Device Profile