Maintenance, Dimensions, Troubleshooting guide – Badger Meter Converters User Manual
Page 4: Control. manage. optimize

1. Install the programming software.
2. Attach the programming cable (
)
to the active sensor through a Com port on your PC.
OTEE:
N
For computers without an RS232 serial port, you may need a USB-to-serial converter.
3. Using a DC power supply, apply 10…30V DC to the active sensor.
4. Start the IFC programming software. The first screen should appear as in
OTEE:
N
If communication fails, check cabling and/or Com port address and try again.
IFC Programming Utility
Setup
Frequency
Device:
Rate Units:
Rate Interval:
K Factor Units:
K Factor:
Damping:
Flow at 4mA:
Flow at 20mA
Linear Points:
Download Setup
Read Setup
Linear Points
Status: Com1
9/23/2008
2:33 PM
0 0 0 0 Hz
Monitor
On
Off
File Options Tools
4-20mA
0-5V
Pulses/Gallon
350.400
0
50.000
0.000
0
Gallons
Minute
IFC Programming Utility
Setup
Frequency
Device:
Rate Units:
Rate Interval:
K Factor Units:
K Factor:
Damping:
Flow at 4mA
Flow at 20mA
Linear Points:
Download Setup
Read Setup
Linear Points
Status: Com1
4/25/2013
2:33 PM
0 0 0 0 Hz
Monitor
On
Off
File Options Tools
4-20mA
0-5V
Pulses/Gallon
350.400
0
50.000
0.000
0
Gallons
Minute
Figure 9: IFC programming screen
5. Press Read Setup to view how the converter is currently programmed.
6. Make any necessary changes and press Download Setup.
MAINTENANCE
1. Make frequent inspections. Create a schedule for maintenance checks based on the environment and frequency of use.
2. Perform visual, electrical and mechanical checks on all components on a regular basis.
a. Visually check for undue heating evidenced by discoloration of wires or other components, damaged or worn parts, or leakage
evidenced by water or corrosion in the interior.
b. Electrically check to make sure that all connections are clean and tight, and that the device is operating correctly.
DIMENSIONS
A
B
Figure 10: Active sensor dimensions
A
B
4.28 in. (109 mm)
1.15 in. (29 mm)
TROUBLESHOOTING GUIDE
Trouble
Remedy
No Current Output
Check polarity of the current loop connections for proper orientation.
Make sure receiving device is configured to provide loop current.
Analog output reads a
constant reading
Make sure there is flow in the system.
Verify that the rotor inside the turbine meter turns freely.
Analog output is not stable
External noise is being picked up by the sensor. Keep all AC wires separate from DC wires.
Check for radio antenna in close proximity. This usually indicates a weak signal.
www.badgermeter.com
Blancett is a registered trademarks of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research,
product improvements and enhancements, Badger Meter reserves the right to change product or system specifications without notice, except to the extent an outstanding
contractual obligation exists. © 2014 Badger Meter, Inc. All rights reserved.
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400
México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882
Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuffen | Germany | +49-7025-9208-0
Europe, Middle East Branch Office | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Office #C209 | Dubai / UAE | +971-4-371 2503
Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411
Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01
Asia Pacific | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836
China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412
Legacy Document Number: 02-SEN-UM-00102-EN
Control. Manage. Optimize.