Unit lifting, Chillers optichill, Installation data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 63
![background image](/manuals/370934/63/background.png)
Chillers
OPTICHILL
™
Chillers
63
Technical Manual : 6530166 V1.6.0 02_2013
Installation Data
UNIT LIFTING
Employ lifting specialists
Local codes and regulations relating to the lifting of this type of equipment should
be observed
Use the appropriate spreader bars/lifting slings (provided by others) with the
holes/lugs provided
Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit
IMPORTANT
Do not use 1 chain between 2 lifting points to avoid load shift.
Only use lifting points provided.
Lifting hole/lug dimension: 40mm
Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage
Lift the unit slowly and evenly
IMPORTANT
If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.
LIFTING DIMENSIONS
2300
A1
C
B
8 - 10 Fan
12 - 20 Fan
A1
C
B
C
A2
2300
A1 (Min)
A2 (Min)
B
C
8 FAN
mm
4000
N/A
520
3200
10 FAN
mm
4000
N/A
846
3500
12 FAN
mm
4000
5000
520
4000
14 FAN
mm
5000
5000
520
4650
16 FAN
mm
5000
5000
520
5000
18 FAN
mm
6000
5000
520
5650
20 FAN
mm
7000
5000
520
6650
IMPORTANT
For models with optional pumps fitted, a separate instruction will be provided.