General specification, Mechanical data - high efficiency, General – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 40: Specification, Optichill ™ chillers, Chillers, Standard chiller - d
![background image](/manuals/370934/40/background.png)
OPTICHILL
™
Chillers
40
Chillers
Technical Manual : 6530166 V1.6.0 02_2013
General Specification
MECHANICAL DATA - HIGH EFFICIENCY
Standard Chiller - D
OPC500HED8
OPC525HED8
OPC550HED8
OPC600HED10
OPC650HED10
Capacity
Nom Output - Cooling Only
(1)
kW
513.2
538.0
562.7
605.1
657.7
Nom Input - Cooling Only
(1)
kW
181.8
194.5
207.3
207.8
220.0
EER
(2)
2.82
2.77
2.71
2.91
2.99
ESEER
(3)
3.59
3.46
3.36
3.48
3.62
ECA Energy Technology listed
Capacity Steps
%
0, 20, 40, 50, 60, 70, 80, 90, 100
Dimensions - H x W x L
mm
2600 x 2200 x
4675
2600 x 2200 x
4675
2600 x 2200 x
4675
2600 x 2200 x
5675
2600 x 2200 x
5675
Weight - Machine
(4)
kg
5360
5380
5410
5900
6150
Weight - Operating
(4)
kg
5600
5640
5650
6170
6570
Construction - Material / Colour
Base: Plain Galvanised Steel
Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint, Light Grey (RAL 7035)
Evaporator
Shell & Tube
Insulation
Class O / UV Stable
Water Volume
l
233.3
233.3
233.3
233.3
383.7
Total Max. Water Flow
l/s
37.7
37.7
37.7
37.7
55.2
Condenser
Copper Tube / Aluminium Fins
Face Area (Total)
m²
20.6
20.6
20.6
25.8
25.8
Nominal Airflow
m³/s
45.6
45.6
45.6
57.0
57.0
Condenser Fan & Motor
Axial - Sickle Bladed Fan
Quantity
8
8
8
10
10
Diameter
mm
800
800
800
800
800
Standard AC Type
Maximum Speed
rpm
900
900
900
900
900
Head Pressure Fan Speed Control
Voltage Regulated
Optional EC Type
Speed Setting
rpm
900
900
900
900
900
Head Pressure Fan Speed Control
Microprocessor Controlled EC (Electronically Commutated) Fans
Compressor
Screw - Twin
Quantity
1 + 1
1 + 1
1 + 1
1 + 1
1 + 1
Oil Charge Volume (Total)
l
22 + 22
19 + 22
19 + 19
19 + 19
19 + 19
Oil Type
Ester Oil
Refrigeration
Dual Circuit
Refrigerant Control
Electronic Expansion Valve (EEV)
Refrigerant Pre Charged
R134a
Charge (Total)
kg
85 + 85
90 + 85
90 + 90
105 + 105
115 + 115
Connections
Grooved type Coupling & Pipe Assembly
Water Inlet / Outlet
DN150 PN16
DN150 PN16
DN150 PN16
DN150 PN16
DN200 PN16
Water Drain / Bleed
in
1/2
1/2
1/2
1/2
1/2
Water System
Min. System Water Volume
(5)
l
1764
1849
1934
2079
2260
Max. System Operating Pressure
bar
10
10
10
10
10
OPTIONAL EXTRAS
Water Pump - ac Motor
(1)
In Line Pump - Fixed Speed Motor
Single Head or Run/Standby
Nom External Head Single - Standard
kPa
70
66
63
56
76
Nom External Head Single - Larger
kPa
107
104
100
94
179
Water Pump - Inverter Driven Motor
In Line Pump - Variable Speed Motor
Single Head or Run/Standby
Nom External Head Single - Standard
kPa
124
120
117
67
87
Nom External Head Single - Larger
kPa
124
120
117
155
174
Overall Dimensions with Pump
- H x W x L
(6)
mm
2600 x 2570 x
6075
2600 x 2570 x
6075
2600 x 2570 x
6075
2600 x 2570 x
7075
2600 x 2570 x
7075
(1)
Based on 12/7°C water temperature and 35°C ambient.
(2)
EER
=
Output kW
Input kW
Where:
Output kW
= Chilled Water Cooling duty.
Input kW
= Compressor + Fan input power.
(3)
ESEER, for further details, refer to
(4)
Based on standard unit, for units fitted with options, please contact Airedale. Machine weight includes refrigerant charge; operating weight includes
refrigerant charge and water volume.
(5)
For minimum system volume calculations, refer to
Minimum system water volume calculations
(6)
-8, -10 & -12 Fan models; pump mounted externally, refer to
, on page 56 for details.