Glycol data, Optichill ™ chillers, Performance data – Airedale OptiChill FreeCool 500kW - 1365kW User Manual
Page 32

OPTICHILL
™
Chillers
32
Chillers
Technical Manual : 6530166 V1.6.0 02_2013
Performance Data
GLYCOL DATA
For a given percentage of glycol in the system there are correction factors that need to
be applied, the following tables can be used as a guide.
CAUTION
The source data must be at 100% Water for the correction factors to be valid.
Ethylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
10% / -4°C
20% / -9°C
30% / -15°C
40% / -23°C
Output (kW)
x
0.98
0.97
0.95
0.93
Compressor Input (kW)
0.99
0.98
0.96
0.95
Water Flow (l/s)
0.99
1.02
1.04
1.07
Pressure Drop (kPa)
1.05
1.20
1.38
1.57
Propylene Glycol Nominal Correction Factors
Glycol in System / Freezing Point ºC
10% / -2°C
20% / -6°C
30% / -12°C
40% / -20°C
Output (kW)
x
0.97
0.95
0.91
0.88
Compressor Input (kW)
0.99
0.98
0.96
0.95
Water Flow (l/s)
0.98
0.97
0.95
0.95
Pressure Drop (kPa)
1.08
1.17
1.31
1.45
Example
Model Ref.
= OPC800HE+D14
Ambient:
= 35°C
Fluid
= 20% Ethylene Glycol
Inlet Fluid Temp.
= 7°C
Outlet Fluid Temp.
= 12°C (5°C
T)
100% Water
Multiplier Corrected Figure
Output (kW)
=
841.2
x 0.97
=
816.0 kW
Compressor Input (kW)
Input (kW) - TFP {283.1 - {14 x 1.7}} =
259.3
x 0.98
=
254.1 kW
Water Flow (l/s)
Output
40.2
x 1.02
=
40.8 l/s
4.19 x
ΔT
Pressure Drop (kPa)
Plot from curve (refer to
33.1
x 1.20
=
39.7 kPa
Where:
Output
= (kW) Output (kW), refer to
Compressor Input
= (kW) Input (kW) refer to
, on page 28, (-) Minus TFP
TFP
(Total Fan Power)
= (kW) Quantity of Fans to unit x Fan Motor Size, refer to
Water Flow
= (l/s) ALWAYS USE 100% water SHC of 4.19.
ΔT
= (°C) Difference of Entering Water and Leaving Water temperature