5.3 Input scaling
InP.1
When using current or voltage signals as input variables for
InP.1 scaling of
input and display values at parameter setting level is required. Specification of
the input value for lower and higher scaling point is in the relevant electrical unit
(mA/ V).
g
Parameters
InL.1 , OuL.1, InH.1 and OuH.1 are only visible if
ConF / InP.1 / Corr = 3 is chosen.
In addition to these settings,
InL.1 and InH.1 can be adjusted in the range
(0...20mA / 0...10V) determined by selection of
S.tYP .
a
For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for
InL.1 and OuL.1 and for InH.1 and
OuH.1 must have the same value.
g
Input scaling changes at calibration level (r page 20) are displayed by input
scaling at parameter setting level. After calibration reset (
OFF), the scaling
parameters are reset to default.
Parameter setting level
TB40-1
19
Input scaling
InP.1
mA/V
phys.
quantity
mA / V
phys. quantity
OuH.x
OuL.x
InH.x
InL.x
S.tYP
Input signal
InL.1
OuL.1
InH.1
OuH.1
30
(0...20mA)
0 … 20 mA
0
any
20
any
4 … 20 mA
4
any
20
any
40
(0...10V)
0 … 10 V
0
any
10
any
2 … 10 V
2
any
10
any