2 configuration 15, Configuration 15, Out.1 – West Control Solutions TB 40-1 Temperature Monitor User Manual
Page 15: Out.2, Logi, Configuration level
Name
Value range Description
Default
20
Pt100 (-200.0 ... 100,0 °C)
21
Pt100 (-200.0 ... 850,0 °C)
22
Pt1000 (-200.0 ... 850.0 °C)
23
special 0...4500 Ohm (preset to KTY11-6 )
24
special 0...450 Ohm
30
0...20mA / 4...20mA 1
40
0...10V / 2...10V 1
S.Lin
Linearization (only at S.tYP = 23 (KTY 11-6), 24
(0...450
W
), 30 (0..20mA), 40 (0..10V) and 41 (0...100mV) )
0
0
none
1
Linearization to specification. Creation of linearization table
with engineering tool possible. The characteristic for KTY
11-6 temperature sensors is preset.
Corr
Measured value correction / scaling
0
0
Without scaling
1
Offset correction (at
CAL level)
2
2-point correction (at
CAL level)
3
Scaling (at
PArA level)
1 with current and voltage input signals, scaling is required
(see chapter 5.3)
Out.1
Name
Value range Description
Default
O.Act
Method of operation OUT1
0
0
direct / normally open
1
inverse / normally closed
Out.2
Name
Value range Description
Default
O.Act
Method of operation OUT2
0
0
direct / normally open
1
inverse / normally closed
LOGI
Name
Value range Description
Default
Err.r
Reset of all limit alarms
6
2
DI1
6
RESET- key
Configuration level
TB40-1
15
Configuration