Alarm adjustments, Control outputs, Display – West Control Solutions MRC 7000 Controller Manual User Manual

Page 71: Record, Digital communications

background image

71

ALARM ADJUSTMENTS

Process Alarm

-9999 to 9999 units

Deviation Alarm

-3000 to 3000 units

Deviation Band Alarm

1 to 3000 units

Hysteresis

0 to 300 units

CONTROL OUTPUTS

Relay SPST

115 VAC: 5.0A Resistive, 1/8HP or 250VA
230 VAC: 2.5A Resistive, 1/8HP or 250VA

SSR Driver

Open collector output
Short circuit protected @ 100mA maximum
Provides 4VDC at 20mA or 3VDC at 40mA

mADC Current

4-20 or 0-20 mADC into 650 ohms maximum load

DISPLAY

Digital Display

Two possible; one per installed pen. Red LED’s 0.56" high.

Status Indicators

LED indicators for Output 1, Output 2, Manual Operation, Alarm,
Setpoint, minus sign and process value units (

°

C,

°

F, or E).

RECORD

Chart

10 in circular chart; 100 charts furnished with each instrument if
standard range

Chart Range

-9999 to 9999

°

/ units

Chart Drive

DC stepper motor

Chart Rotation

User configurable from 0.1 to 999.9 hours per revolution

Pen Type

Disposable Fiber-tip

Pen Color

Pen 1-Red, Pen 2-Green

Pen Response Time

< 9 seconds over chart span

Accuracy

±

1.0% of chart span max. error from displayed value

Chart Rotation Accuracy

±

0.5% of Chart Rotation Time

DIGITAL COMMUNICATIONS

Type

RS-422/485 serial communications port. Half-duplex bi-directional
communications.

Character Format

ASCII

Protocol

Per ANSI X3.28 subcategories 2.5 & A4

Configuration

User configurable to Monitor (read only) or Normal (read and write)

Bit Rate

User configurable to 300, 600, 1200, 2400, 4800, or 9600 bits per
second

Address

User configurable for each pen; 0 to 99