West Control Solutions MRC 7000 Controller Manual User Manual

Page 29

background image

29

4

Output 1 Percent

o1uL

0 to 100 percent

100

Upper Limit
(o1uLand o1LL will
not be seen if out1 = 0,1,2)

5

Output 1 Percent

o1LL

0 to 100 percent

0

Lower Limit

6

Output 2

out2

0 = None (Position

0

Proportioning - Direct Closed)

1=On-Off- Direct
2=On-Off- Reverse
3=Time Proportioning- Direct
4=Time Proportioning-Reverse
5=Current Proportioning- Direct
6=Current Proportioning -Reverse
7=Position Proportioning
(Reverse/Closed)

7

Output 2 Percent

o2uL

0 to 100 percent

100

Upper Limit (o2uL and
o2LL will not been seen if
out2 = 0,1,2,7)

8

Output 2 Percent

o2LL

0 to 100 percent

0

Lower Limit

9

Alarm 1

AL1

0 to 6

0

the Alarm Point

0 = None

is selected in the

1=Process Alarm-Direct

Tune mode

2=Process Alarm-Reverse
3=Deviation Alarm-Direct
4=Deviation Alarm-Reverse
5=Deviation Band Alarm-Open within band
6=Deviation Band Alarm-Closed within band

10

Alarm 2

AL2

Same selections as Alarm 1

0

11

Display Select

diSP

1=Process value only

1

2=Process value/setpoint
3=Deviation only
4=Deviation and setpoint
5=Setpoint only

12

Decimal Position

dPoS

0 to 3

0

0=None
1=One decimal place
2=Two decimal places
3=Three decimal places
RTD and thermocouple inputs
are limited to either 0 or1 decimal positions

13

Engineering Units

Euu

-9999 to 9999

1000

Upper Value (Euu and
EuL will be seen if the pen
input select = 30,31,32,33,34)

14

Engineering Units

EuL

-9999 to 9999

0

Lower Value

15

Hysteresis for

HyCo

0 to 300

3

Control Outputs

Width of Hysteresis Band
(See page 66 for definition)

DISPLAY AVAILABLE

FACTORY YOUR

STEP

DESCRIPTION

CODES SETTINGS

SETTING SETTING