Input specifications – West Control Solutions MRC 7000 Controller Manual User Manual
Page 70

70
Input Specifications
THERMOCOUPLE
TYPE
RANGE
TYPE
RANGE
J
0 to 760C
E
0 to 750C
0 to 1400F
0 to 1400F
K
0 to 1360C
B
200 to 1800C
0 to 2500F
400 to 3300F
T
-220 to 400C
N
0 to 1300C
-330 to 750F
0 to 2370F
R
200 to 1650C
C
200 to 2300C
400 to 3000F
390 to 4170F
S
200 to 1650C
400 to 3000F
MILLIAMPS
MILLIVOLTS
RTD
4-20 mADC
0 TO 25 mV
100 OHM
(with resistor)
0 to 50 mV
(.00385 OHMS/OHM/C)
10 to 50 mV
-140 to 400C
VOLTS
REMOTE SETPOINT
0 to 5 VDC
0 to 5 VDC
1 to 5 VDC
1 to 5 VDC
CONTROL ADJUSTMENTS
Proportional Band
1 to 3000 units
Manual Reset
-1500 to 1500 units
Auto Reset (Integral)
0.0 to 100.0 repeats per minute
Rate (Derivative)
0.0 to 10.0 minutes
Cycle Time
1 to 240 seconds
Position Proportioning
Sensitivity
0.0 to 50.0%
On/Off Hysteresis
0 to 300 units
(width of hysteresis band)
First Output Position
-1000 to 1000 units
Second Output Position
-1000 to 1000 units
Automatic
User selectable to transfer from manual to
Transfer Function
automatic control when setpoint is reached
Can be disabled.
Auto/Manual
Bumpless transfer from automatic to manual.
Manual Output
0 to 100%