West Control Solutions MRC 7000 Controller Manual User Manual
Page 31

31
33
Pen Action on
PAEC
0 or 1
1
Error Condition
0 = Pen goes to 0 % of chart
1 = Pen goes to 100 % of chart
Pressing the SCROLL key with the PAEC parameter value displayed in the Pen 1 window will
advance the display of a single pen instrument to the unit parameters. Pressing the SCROLL
key with the PAEC parameter displayed in the Pen 1 window of a two pen instrument will
advance the display to be PEns in the Pen 2 window. The Pen 2 Program mode parameter
selections can be made now. Pressing the SCROLL key with the PAEC parameter value
displayed in the Pen 2 window will cause the display to advance to the unit parameters
displayed in the Pen 1 window.
UNIT PARAMETERS
34
Relay A Assignment
rLyA
0 to 8
0
1=Assigned to Alarm 1-Pen 1
2=Assigned to Alarm 2-Pen 1
3=Assigned to Alarm 1-Pen 2
4=Assigned to Alarm 2-Pen 2
5=Assigned to Output 1-Pen 1
6=Assigned to Output 2-Pen 1
7=Assigned to Output 1-Pen 2
8=Assigned to Output 2-Pen 2
35
Relay B Assignment
rLyb
Same selection as rLyA
0
36
Relay C Assignment
rLyC
Same selection as rLyA
0
37
Relay D Assignment
rLyd
Same selection as rLyA
0
38
Relay E Assignment
rLyE
Same selection as rLyA
0
39
Relay F Assignment
rLyF
Same selection as rLyA
0
40
Relay G Assignment
rLyg
Same selection as rLyA
0
41
Relay H Assignment
rLyH
Same selection as rLyA
0
42
Current Output A
CurA
0 to 6
0
Assignment
0=Not Assigned
1=Assigned to Process
Value Output-Pen 1
2=Assigned to Process
Value Output-Pen 2
3=Assigned to Output 1-Pen 1
4=Assigned to Output 2-Pen 1
5=Assigned to Output1-Pen 2
6=Assigned to Output 2-Pen 2
43
Current Output B
Curb
Same selection as CurA
0
Assignment
44
Current Output C
CurC
Same selection as CurA
0
Assignment
45
Current Output D
Curd
Same selection as CurA
0
Assignment
46
Current Output A
CoAr
0 to 1
1
Range
0=0-20 mA
1=4-20 mA
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODES SETTINGS
SETTING SETTING