D.1.3, Range, D.1.4 – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual
Page 71: Charging the battery, Table 26: sensitivity ranges, D.1.3 range, D.1.4 charging the battery
TM 40/40L, Rev (6) February 2013
Long Range UV/IR Fire Simulator
59
D.1.3 Range
Table 26: Sensitivity Ranges
Detector
Model
Standard Test
Range(ft./m)
Extended Test
Range with
collimator
(ft./m)
40/40L
14.5/4.5
29/9
40/40LB
14.5/4.5
29/9
40/40L4
2.4/0.75
N/A
40/40 L4B
2.4/0.75
N/A
Notes:
The minimum distance from the detector is 20 inches (50 cm).
The optional beam collimator is fitted for Extended Range.
At extreme temperatures, there is a 15% maximum reduction in the
range.
Important: Keep the Fire Simulator in a safe place when not in use.
D.1.4 Charging the Battery
The Fire Simulator uses NiCd batteries as a rechargeable power source.
When the batteries are fully charged, the simulator operates for at least 60
times without recharging. An internal buzzer is sounded when the voltage
from the batteries is lower than the required operational level.
➣
To charge the battery:
1
Place the Fire Simulator on a table in a safe area.
2
Turn the sealed plug (next to the operation button) counter-clockwise
with a suitable wrench.
3
Connect the battery charger.
4
Charge for a maximum of 14 hours.
5
Disconnect the charger.
6
Tighten the sealed plug clockwise.
Warning: Charge the simulator only when the battery is fully discharged.
During activation of the flame simulator, buzzer activation indicates that the
battery is discharged.