beautypg.com

4 manual bit only selected, Table 11: results of a successful manual bit, Table 12: results of an unsuccessful manual bit – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 30: Table 11, Table 12

background image

SharpEye

TM

UV/IR Flame Detector User Guide

18

Internal Detector Tests

Table 11: Results of a Successful Manual BIT

Output

Result

FAULT relay

Wiring options 1, 2, and 4: remains CLOSED (Normal)

Wiring options 3 and 5: remains OPEN (Normal)

ALARM relay

Activated for 3 sec (only when the function Alarm BIT is

set to YES)

AUXILIARY

relay

For wiring options 4 and 5: is activated for 3 sec (only

when the function Auxiliary BIT is set to YES)

0-20mA

output

Wiring option 1, 2, 3:

Initiates 20 mA only when the function Alarm BIT is set
to YES

Initiates 16 mA when the function Auxiliary BIT is set
to YES and the function Alarm BIT is set to NO

POWER LED

Green, Flashing, 1 Hz

Table 12: Results of an Unsuccessful Manual BIT

Output

Result

FAULT relay

Wiring option 1, 2, 4: changes to OPEN

Wiring option 3 and 5:changes to CLOSED

0-20mA
output

Wiring option 1, 2, 3: Indicates BIT FAULT (2mA)

POWER LED

Yellow, Flashing, 4 Hz

1.6.2.4 Manual BIT only selected

The BIT is initiated manually by momentarily connecting Terminal Number 3
with Terminal Number 2 or a switch across these terminals in the safe area.