Internal Detector Tests
Table 11: Results of a Successful Manual BIT
Output
Result
FAULT relay
Wiring options 1, 2, and 4: remains CLOSED (Normal)
Wiring options 3 and 5: remains OPEN (Normal)
ALARM relay
Activated for 3 sec (only when the function Alarm BIT is
set to YES)
AUXILIARY
relay
For wiring options 4 and 5: is activated for 3 sec (only
when the function Auxiliary BIT is set to YES)
0-20mA
output
Wiring option 1, 2, 3:
Initiates 20 mA only when the function Alarm BIT is set
to YES
Initiates 16 mA when the function Auxiliary BIT is set
to YES and the function Alarm BIT is set to NO
POWER LED
Green, Flashing, 1 Hz
Table 12: Results of an Unsuccessful Manual BIT
Output
Result
FAULT relay
Wiring option 1, 2, 4: changes to OPEN
Wiring option 3 and 5:changes to CLOSED
0-20mA
output
Wiring option 1, 2, 3: Indicates BIT FAULT (2mA)
POWER LED
Yellow, Flashing, 4 Hz
1.6.2.4 Manual BIT only selected
The BIT is initiated manually by momentarily connecting Terminal Number 3
with Terminal Number 2 or a switch across these terminals in the safe area.