D.1.1, Unpacking, D.1.2 – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual
Page 70: Operating instructions, D.1.1 unpacking, D.1.2 operating instructions
SharpEye
TM
UV/IR Flame Detector User Guide
58
Long Range UV/IR Fire Simulator
D.1.1 Unpacking
Verify that you have received the following contents:
Delivery form
Fire Simulator with integral batteries
Battery charger
Optional Beam Collimator
Storage case
D.1.2 Operating Instructions
Warning: Do not open the Fire Simulator to charge the batteries or for any
other reason in a hazardous area.
Caution: The following test simulates a real fire condition and may activate
the extinguishing system or other alarms. If this is not desired,
disconnect/inhibit them before the test and reconnect after the simulation.
➣
To simulate a fire:
1
Aim the Fire Simulator towards the detector’s Target Point
Figure 16: 40/40L, LB, L4, L4B UV/IR Detector Target Point
2
When testing keep a distance of at least 50 cm (20 inches) from the
detector.
3
Press the operation button once. Fire simulation lasts for 20 seconds.
The detector sends an alarm signal (solid red LED).
4
Wait 20 seconds before repeating the test.
5
Verify that the optical window is clean.
Target Point