beautypg.com

A specifications, Specifications, Technical specifications – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 55: Aspecifications, A.1 technical specifications

background image

Technical Specifications

43

A

Specifications

In this appendix…

Technical Specifications

page 43

Electrical Specifications

page 44

Outputs

page 44

Approvals

page 47

Mechanical Specifications

page 47

Environmental Specifications

page 47

A.1

Technical Specifications

Spectral Response

40/40L-LB UV:0.185 – 0.260µm IR:2.5 - 3.0µm
40/40L4-L4B UV:0.185 – 0.260µm IR:4.4 - 4.6µm

40/40L-LB

Detection Range

(at highest Sensitivity
Setting for 1ft

2

(0.1m

2

) pan

fire)

Fuel

ft. / m

Fuel

ft. / m

Gasoline

50 / 15

Methanol

25 / 7.5

n-Heptane

50 / 15

Methane *

15 / 4.5

JP5

37 / 11

LPG *

15 / 4.5

Kerosene

37 / 11

Paper

15 / 4.5

Diesel Fuel

37 / 11

Polypropylene

15 / 4.5

Alcohol 95%

25 / 7.5

Hydrogen*

15 / 4.5

IPA

25 / 7.5

* 20" (0.5m) high, 8" (0.2m) width plume fire

40/40L4-L4B
Detection Range

(at highest Sensitivity
Setting for 1ft

2

(0.1m

2

) pan

fire)

Fuel

ft. / m

Fuel

ft. / m

Gasoline

66 / 20

IPA

52 / 16

n-Heptane

66 / 20

Methanol

39 / 12

JP5

49 / 15

Methane *

26 / 8

Kerosene

49 / 15

LPG *

23 / 7

Diesel Fuel

49 / 15

Paper

23 / 7

Alcohol 95%

39 / 12

Polypropylene

16 / 5

* 20" (0.5m) high, 8" (0.2m) width plume fire

Response Time

Typically 5 seconds for models 40/40L-LB.
Typically 3 seconds for models 40/40L4-L4B.

Adjustable Time Delay Up to 30 seconds