beautypg.com

Approvals, Mechanical specifications, Environmental specifications – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 59: A.4 approvals, A.5 mechanical specifications, A.6 environmental specifications

background image

TM 40/40L, Rev (6) February 2013

Troubleshooting

47

A.4

Approvals

Hazardous Area

Approvals

FM, CSA
Class I Div. 1 Groups B, C and D;
Class II/III Div. 1 Groups E, F and G.

ATEX, IECEx
Ex II 2 G D
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
or
Ex de IIC T4 Ta -55°C to +85°C

Functional

Approvals

EN54-10 approved by VdS

FM approved per FM3260

A.5

Mechanical Specifications

Enclosure

Stainless Steel 316
or
Aluminum, heavy duty copper free (less than 1%),
red epoxy enamel finish

Water and Dust

Tight

NEMA 250 type 6p.

IP 66 and IP 67 per EN 60529

Electronic

Modules

Conformal coated

Electrical

Connection
(two entries)

¾" - 14NPT conduit
or

M25 x 1.5

Dimensions

4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)

Weight

Stainless Steel: 6.1 lb. (2.8 kg)

Aluminium: 2.8 lb. (1.3 kg)

A.6

Environmental Specifications

The SharpEye 40/40L, LB, L4, L4B is designed to withstand harsh
environmental conditions.

High Temperature

Designed to meet MIL-STD-810C, method
501.1 procedure II

Operating temperature: +167°F (+75 °C)

Storage temperature: +185 °F (+85 °C)

Low Temperature

Designed to meet MIL-STD-810C, method
502.1, procedure I

Operating temperature: -57°F (-50°C)

Storage temperature: -65°F (-55°C)