Approvals, Mechanical specifications, Environmental specifications – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual
Page 59: A.4 approvals, A.5 mechanical specifications, A.6 environmental specifications
TM 40/40L, Rev (6) February 2013
Troubleshooting
47
A.4
Approvals
Hazardous Area
Approvals
FM, CSA
Class I Div. 1 Groups B, C and D;
Class II/III Div. 1 Groups E, F and G.
ATEX, IECEx
Ex II 2 G D
Ex de IIC T5 Ta -55°C to +75°C
Ex tD A21 IP66/X7 T95°C
or
Ex de IIC T4 Ta -55°C to +85°C
Functional
Approvals
EN54-10 approved by VdS
FM approved per FM3260
A.5
Mechanical Specifications
Enclosure
Stainless Steel 316
or
Aluminum, heavy duty copper free (less than 1%),
red epoxy enamel finish
Water and Dust
Tight
NEMA 250 type 6p.
IP 66 and IP 67 per EN 60529
Electronic
Modules
Conformal coated
Electrical
Connection
(two entries)
¾" - 14NPT conduit
or
M25 x 1.5
Dimensions
4" x 4.6" x 6.18" (101.6 x 117 x 157 mm)
Weight
Stainless Steel: 6.1 lb. (2.8 kg)
Aluminium: 2.8 lb. (1.3 kg)
A.6
Environmental Specifications
The SharpEye 40/40L, LB, L4, L4B is designed to withstand harsh
environmental conditions.
High Temperature
Designed to meet MIL-STD-810C, method
501.1 procedure II
Operating temperature: +167°F (+75 °C)
Storage temperature: +185 °F (+85 °C)
Low Temperature
Designed to meet MIL-STD-810C, method
502.1, procedure I
Operating temperature: -57°F (-50°C)
Storage temperature: -65°F (-55°C)