Performance Considerations

13

1.5.5 Output Signals

Outputs are available according to the default configuration or the wiring
options selected for the 40/40L, LB, L4, L4B detector. Determine the
outputs for your model according to Table 6.

The detector incorporates several types of output suitable to different

control systems:

0-20mA (stepped) with HART

Relays (Alarm, Fault, Auxiliary)

RS-485 Modbus

Table 6: Available Output Types

Output Type

Version

Detector Status

Alarm relay

40/40L, LB, L4, L4B –
Options 1XXXX, 4XXXX,

5XXXX

The relay is N.O.

40/40L, LB, L4, L4B –

Options 2XXXX, 3XXXX

The relay is N.O. and N.C.

Auxiliary relay

40/40L, LB, L4, L4B –

Options 4XXXX and
5XXXX

The relay is N.O.

Fault relay

40/40L, LB, L4, L4B –

Options 1XXXX, 2XXXX,
4XXXX

The relay is N.C. energized

40/40L, LB, L4, L4B –

Options 3XXXX, 5XXXX

The relay is N.O. energized

0-20mA

current output

40/40L, LB, L4, L4B –

Option 1XXXX

SINK Option, (can be

changed to Source – see
Figure 10, Figure 11 and

Figure 12)

40/40L, LB, L4, L4B –

Options 2XXXX and
3XXXX

SOURCE Option with the

HART protocol

RS-485

All versions

Modbus protocol