beautypg.com

Table 25: wiring connections – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 64

background image

SharpEye

TM

UV/IR Flame Detector User Guide

52

Typical Wiring Configurations

Table 25: Wiring Connections

Wiring
Option

Detector

Model

Terminals

5

8

9

1

40/40L, LB, L4,

L4B-1XXXX

Fault Relay

(N.C)

0-20mA

(Sink)

0-20mA

(Sink)

2

40/40L, LB, L4,

L4B-2XXXX

Fault Relay

(N.C)

Alarm Relay

(N.C)

0-20mA

Source

3

40/40L, LB, L4,

L4B-3XXXX

Fault Relay

(N.O)

Alarm Relay

(N.C)

0-20mA

Source

4

40/40L, LB, L4,

L4B-4XXXX

Fault Relay

(N.C)

Auxiliary

Relay (N.O)

Auxiliary

Relay N.O.

5

40/40L, LB, L4,

L4B-5XXXX

Fault Relay

(N.O)

Auxiliary

Relay (N.O)

Auxiliary

Relay N.O.

Figure 9: Typical Wiring for 4 Wire Controllers (Using Option 1 or 2
Wiring)