6.6 Description of unit functions
The following table contains a listing and description of all functions of the HART

protocol that can be used for setting up the

temperature transmitter. Note: Factory default values are shown in bold text. The HART

operating module (DXR275) display is

indicated by the following symbol.

Function group: WORKING PARAMETERS

Primary value

• V0H0

• (PV)

Display of actual measured temperature
Display: 7-digit number with floating decimal point and engineering unit.
(e.g. 199.98 Ohm; -62.36 deg. C)

Int. temperature

• V0H1

Display of the actual measured temperature of the internal comparison measurement point.

Filter time

• V0H2

Digital filter selection 1

st

grade.

Input: (0 to 100) seconds
0 s

RJ Mode

• V0H3

Selection of internal (Pt100) or external (0 to 80)

°C cold junction compensation.

Entry: Internal; External
Internal

RJ External Value

• V0H4

Entry of external cold junction value.
Entry: (-40.00 to 85.00)

°C (°C, °F, K)

0.00

°C


Hint! Entry only possible on selection of an external cold junction compensation in unit function
RJ MODE.

Bias Input (Offset)

• V0H5

Entry of zero point correction (Offset).
Entry: (-10.00 to 10.00)

°C (°C, °F, K)

0.00

°C


Hint! Entry returns to factory default values when changing sensor type!