beautypg.com

Pyromation Series 442 User Manual

Page 4

background image

Copyright 2006 Pyromation, Inc., All rights reserved.

4 of 11

Phone (260) 484-2580

FAX (260) 482-6805 or (800) 837-6805

www.pyromation.com

442-D



6.4 Quick Setup
The head transmitter left the factory with a default parameter configuration. If no customer specific configuration was mentioned on
the order then the default parameter configuration is constructed as follows:

Sensor

Pt100 (RTD)

Connection mode

3-wire

Measurement range and units

(0 to 100) °C


Using the Quick Setup the operator is led through all the most important unit functions that must be setup for standard
measurement operation of the unit. Using the HART

hand module a quick set-up of the black highlighted fields of the HART

function matrix (see figure 6-2) is possible.

• Type of sensor

(V2H0)

• Unit meas. Value (V2H2)
• Value of 4 mA

(V2H4)

• Value of 20 mA

(V2H5)

• Connection

(V2H6)


6.5 Configuration with HART

protocol

Selection of all head transmitter functions using the HART

hand module is done with various menu levels with the help of the

Pyromation function matrix (see figure 6-2). All head transmitter functions are described in 6.6, Description of unit functions.

What needs to be done:
1. Switch on the hand module:

- Measurement unit is not yet connected. The HART

main menu appears. This menu level appears for all HART

programming independent of the type of instrumentation. Information to offline programming can be found in the
“Communicator DXR 275/375 operating manual.

- Measuring unit is connected. The menu level “Online” appears. In this “Online” menu level the actual measured data such

as measured value (PV) and output current (AO) are continuously displayed. Entry into the Series 442 operating matrix is
done using the line “Matrix parameters”. This matrix systematically contains all HART

accessible functions.

2. Using “Matrix parameters” the function group can be selected (e.g. basic calibration) and then followed by the required

function, e.g. “Sensor input”.

3. Enter numeric values or change settings. Then acknowledge using the F4 “Entry” function key.
4. “SEND” appears when operating the F2 function key. Once the F2 key has been operated all values entered in the hand

module are transmitted to the Series 442 measurement system.

5. A return to the “Online” menu level is made using the F3 “HOME” function key. Here, the actual transmitter values measured

with the new settings can be read.

Figure 6-1

Configuration at the hand module example “Sensor input”