NSi Industries ELC72 User Manual
Page 14

12
• NONE: not used
• On\d: On with off delay override (Recommended
for a momentary switch closure to turn the load ON
with a countdown to OFF . Maintain switch closure
holds load ON until switch opens and starts
countdown to OFF)
• OVr: Toggle override (First maintained switch closure
turns load ON and second switch closure turns load
OFF . Can include a countdown to OFF .)
• ENb: Enabler input (a maintained switch closure
allows channel to follow program)
• F: Fahrenheit temperature sensor
• C: Celsius temperature sensor
• L: Light level sensor
• U: User defined sensor (Used with TORK EPC-LC light
sensor)
Press the PROGRAM key to bypass and go to next
mode .
Press the NEXT key to go to the first setting .
5.1 SET INPUTS
Use the + and - keys to modify the flashing item .
Use the NEXT key advance to the next flashing item .
Choose the desired input type with the + and - keys
then the NEXT key .
• On\d (On with off delay override) next screen is used
for setting the off delay time when the input is
configured as an On\d override type. The off delay is
programmable from 0 seconds to 23 hours, 59
minutes and 59 seconds .
Select On\d.
Program hours, minutes, or seconds .