KEY FUNCTIONS

DAY/MONTH: Press to advance the day in the CLK
mode. Press to advance the Month in the DATE
mode.

HOUR/DATE: Press to set the Hours in the CLK
mode and in the Schedule SET mode. Press to
advance Date in the DATE mode.

MIN/YEAR: Press to set the Minute in the CLK mode
and in the Schedule SET mode. Press to advance
Year in the DATE mode.

OVERRIDE: Press to alter the Load status and/or to
Override scheduled event.

MODE: Press to advance to next mode without
affecting the scheduled memory information.
Sequence is: RUN, CLK, DATE, schedule SET. In
the SET mode, unit automatically reverts to the
RUN mode if no entries are made for 5 minutes.

SP DAY: Press during RUN mode to execute the
“SPECIAL DAY” schedule everyday. LCD will display
D in upper right corner. Pressing SP DAY again will
toggle the unit back to normal 7 day program opera-
tion.

ON/OFF: Pressing each time will select ON or OFF
event. Multiple OFFs may be scheduled to cancel
override ON’s.

ENTER: Press to store the displayed information into
memory. Information will not be stored until
ENTER is pressed.

NOTE: During settings, each press of the key will
advance one number. For rapid advance, hold key in.

2

DAY

MONTH

HOUR

DATE

MIN

YEAR

OVER-

RIDE

MODE

SP

DAY

ON/

OFF

ENTER

TORK DG100 / DG120

DIGITAL TIME SWITCH

SEVEN DAY

READ INSTRUCTIONS CAREFULLY BEFORE SETTING UNIT

FEATURES

Single channel controller

7 day scheduling

Special day scheduling

32 set points

Battery back-up uses standard 9 volt non-recharge-
able (not supplied). Lithium averages 450 hours of
power outage; Alkaline averages 175 hours

Manual override to the next scheduled event

Automatic daylight saving - user selectable

Automatic leap year compensation

AM/PM or 24 hour format - user selectable

INSTALLATION

UNIT IS TO BE INSTALLED BY A LICENSED ELECTRICIAN

1. To remove unit from enclosure: Push tab on right

to swing unit to the left and remove.

2. Mount the enclosure at eye level using screws or

other suitable fastening device. Bring supply and
load wires in through bottom or side knockouts.
DO NOT USE TOP.
Input wires to controller must be dedicated i.e. no
other loads connected to the same circuit.

3. Install a standard 9 volt lithium or alkaline battery

(not supplied) by gently squeezing the right side of
the battery cover on the front of the unit and pull
to open. Pull out the battery connector and con-
nect the battery. Reinstall battery cover. Lithium
should be replaced every 3-5 years, Alkaline
every year.

NOTE: Unit can be fully programmed using battery
power only.

4. Reinstall unit by reversing step #1 above and con-

nect wires to unit as per suggested wiring dia-
grams. See illustration on enclosure label.