Ufc500 conformance and command class summary – KROHNE UFC 500 HART User Manual
Page 6
HARTô Smart Communications Protocol
UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001
© 2001 KROHNE Mefltechnik D-47058 Duisburg
Page
6
3. UFC500 Conformance And Command Class Summary
Command
Description
Number
CONFORMANCE CLASS #1
- UNIVERSAL
0
Read Unique Identifier
1
Read Primary Variable
CONFORMANCE CLASS #1A
- UNIVERSAL
0
Read Unique Identifier
2
Read Primary Variable Current and Percent of Range
CONFORMANCE CLASS #2
- UNIVERSAL
11
Read Unique Identifier Associated with Tag
12
Read Message
13
Read Tag, Descriptor, Date
14
Read Primary Variable Sensor Information
15
Read Primary Variable Output Information
16
Read Final Assembly Number
CONFORMANCE CLASS #3
- UNIVERSAL
3
Read All Dynamic Variables and Current
- COMMON-PRACTICE
33
Read Transmitter Variables
48
Read Additional Transmitter Status
50
Read Dynamic Variable Assignments
60
Read Analog Output and Percent of Range
- TRANSMITTER-SPECIFIC
130
Read Meter Size
132
Read Frequency/Pulse Output Damping Value
134
Read Analog Output Low Flow Cutoff Control and Values
138
Read Analog Output Function
140
Read Current Output Parameters
142
Read Frequency/Pulse Output Parameters
146
Read Flow Direction and Primary Head Constant
148
Read User Data
153
Read Error List
156
Read Device-Specific Units and Enumerators
158
Read Transmitter Variable Range Values
CONFORMANCE CLASS #4
- COMMON-PRACTICE
34
Write Primary Variable Damping Value
35
Write Primary Variable Range Values
36
Set Primary Variable Upper Range Value
38
Reset Configuration Changed Flag
66
Enter/Exit Fixed Analog Output Mode
- TRANSMITTER-SPECIFIC
133
Write Frequency/Pulse Output Damping Value
137
Reset Totalizers
150
Enable/Disable Password Protection
152
Quit Errors
159
Write Transmitter Variable Range Values
CONFORMANCE CLASS #5