2 command #131 write meter size – KROHNE UFC 500 HART User Manual
Page 16

HARTô Smart Communications Protocol
UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001
© 2001 KROHNE Mefltechnik D-47058 Duisburg
Page
16
8.2
Command #131
Write Meter Size
Changes of the converter meter size will force the updating of sensor characteristics (returned by Command #14) and
therefore might cause the automatic correction of the Primary Variable Upper Range Value (Menus 1.1.1, 3.1.1) and
PulseValue (Menu 3.4.3). Master is prompted about corrections carried out via warning responses and must reread the
updated data. For additional information refer to Command #35.
REQUEST DATA BYTES
#0
#1
#2
#3
METER
METER
SIZE
SIZE
MSB
LSB
RESPONSE DATA BYTES
#0
#1
#2
#3
METER
METER
SIZE
SIZE
MSB
LSB
Data Byte #0-#3
Meter size, IEEE 754, in meters. Allowed settings: 0.025 to 4 meters (0.98 to 157.48 inches).
COMMAND-SPECIFIC RESPONSE CODES
0
No Command-Specific Errors
1-2
Undefined
3
Passed Parameter too Large
4
Passed Parameter too Small
5
Too Few Data Bytes Received
6
Local Device User
7
In Write Protect Mode
8-113
Undefined
114
Range Exceeded Max and Was Corrected
115
Range Surpassed Min and Was Corrected
116
Both Range and Pulse Value Corrected
117-127 Undefined