beautypg.com

KROHNE UFC 500 HART User Manual

Page 40

background image

HARTô Smart Communications Protocol

UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001

© 2001 KROHNE Mefltechnik D-47058 Duisburg

Page

40

8.21

Command #153

Read Error List

Unlike Command #48, Read Additional Transmitter Status, where status information is ìmixedî, this command returns a
complete list of error messages: the actual errors are being active at response time; errors that become inactive but are
not quitted, are preserved in a list of ìstoredî errors.

Both actual and stored lists have identical structure. Therefore they are considered below together.

REQUEST DATA BYTES

NONE

RESPONSE DATA BYTES

#0

#1

#2

#3

ACTUAL

ACTUAL

STORED

STORED

ERRORS

ERRORS

ERRORS

ERRORS

#1

#2

#1

#2

Data Byte #0/#2

Bit-mapped actual/stored error byte #1 (bit #7 is MS bit):
Bit #7

Fuse error

Bit #6

Data error in EEPROM 2 (totalizer)

Bit #5

Current calibration values in EEPROM 1+2 are different

Bit #4

Current output overranged

Bit #3

Frequency/pulse output overranged

Bit #2

US path 2 faulted

Bit #1

Empty pipe

Bit #0

US path 1 faulted

Data Byte #1/#3

Bit-mapped actual/stored error byte #2 (bit #7 is MS bit):
Bit #7

Checksum error in ROM

Bit #6

Checksum error in RAM

Bit #5

NVRAM error

Bit #4

Calibration data lost

Bit #3

Data error in EEPROM 1 (parameters)

Bit #2

Irregular flow

Bit #1

Counts lost or totalizer overflow

Bit #0

Power failure

COMMAND-SPECIFIC RESPONSE CODES

0

No Command-Specific Errors

1-5

Undefined

6

Local Device User

7-127