beautypg.com

KROHNE UFC 500 HART User Manual

Page 18

background image

HARTô Smart Communications Protocol

UFC500 Command Specification Rev: 2.0 Release Date: 9 Jun 2001

© 2001 KROHNE Mefltechnik D-47058 Duisburg

Page

18

8.4

Command #133

Write Frequency/Pulse Output Damping Control

Defines the damping value to be used on device frequency/pulse output.

REQUEST DATA BYTES

#0
FREQ/PULSE
DAMPING
CONTROL

RESPONSE DATA BYTES

#0
FREQ/PULSE
DAMPING
CONTROL

Data Byte #0

Damping control for the frequency/pulse output:
0 - Damping value is fixed to 40 ms,
Any other value - The same as for current output (Primary Variable Damping Value).

COMMAND-SPECIFIC RESPONSE CODES

0

No Command-Specific Errors

1-4

Undefined

5

Too Few Data Bytes Received

6

Local Device User

7

In Write Protect Mode

8-127

Undefined