beautypg.com

Technical data – KROHNE OPTIMASS 2400 User Manual

Page 39

background image

TECHNICAL DATA

6

39

OPTIMASS 2400

www.krohne.com

07/2014 - 4003533101- MA OPTIMASS 2400 R01 en

Linear de-rating of PED certified secondary containment

Flanges

• DIN flange ratings are based on EN 1092-1 2007 table G.4.1 material group 14EO
• ASME flange ratings are based on ASME B16.5 2003 table 2 material group 2.2
• JIS flange ratings are based on JIS 2220: 2001 table 1 division 1 material group 022a

Notes

• The maximum operating pressure will be either the flange rating or the measuring tube

rating, WHICHEVER IS THE LOWER!

WHICHEVER IS THE LOWER!

WHICHEVER IS THE LOWER!

WHICHEVER IS THE LOWER!

• The manufacturer recommends that the seals are replaced at regular intervals. This will

maintain the hygienic integrity of the connection.

Pressure / temperature de-rating, all meter sizes, in imperial (flanged connections as

Pressure / temperature de-rating, all meter sizes, in imperial (flanged connections as

Pressure / temperature de-rating, all meter sizes, in imperial (flanged connections as

Pressure / temperature de-rating, all meter sizes, in imperial (flanged connections as
per ASME B16.5)

per ASME B16.5)

per ASME B16.5)

per ASME B16.5)

X temperature [°F]
Y pressure [psig]

1 Measuring tube (UNS S32760) PED certification
2 Measuring tube (UNS S31803) PED certification
3 Measuring tube (UNS S31803 / S32760) FM certification
4 Measuring tube (UNS S31803) CRN certification

Outer cylinder material

-49°F

68°F

266°F

304 / L or 316 / L

580 psig

580 psig

464 psig

UNS S31803

2175 psig

2175 psig

1450 barg

MA_OPTIMASS_2400_en_140515_4003533101_R01.book Page 39 Thursday, July 31, 2014 5:08 PM