SAFETY-RELATED CHARACTERISTICS

7

15

TT 51 SERIES

www.krohne.com

09/2010 - 4000869801 - AD TT 51 SIL R01 en

Single RTD 2/3w sensor

Dual RTD 3w sensor with activated sensor drift monitoring

Failure category

SFF PFD

avg

at T

proof

=

PFH

SIL AC

λ

SD

λ

SU

λ

DD

λ

DU

[FIT]

[%]

1 year

2 years

5 years

10 years

Close

coupled low

stress

0

146 427

49

92.1

2.44E-04

4.57E-04

1.09E-03

2.16E-03

4.90E-08

SIL 2

Close

coupled high

stress

0

146 1175 213

86.1

1.05E-03

1.97E-03

4.74E-03

9.36E-03

2.13E-07

(SIL 2)

Extension

wires low

stress

0

146 768

135

87.1

6.63E-04

1.25E-03

3.00E-03

5.93E-03

1.35E-07

(SIL 2)

Extension

wires high

stress

0

146 7988 1940 80.7

9.45E-03

1.79E-02

4.31E-02

8.52E-02

1.94E-06

(SIL 1)

The boxes marked in light grey in the following tables mean that the calculated PFD

avg

and/or

PFH values are within the allowed range for SIL 2 according to table 2 / 3 of IEC 61508-1 but do not
fulfill the requirement to not claim more than 35% of this range, i.e. to be better than or equal to
3.50E-03 respectively 3.50E-07 1/h.
The boxes marked in medium grey mean that the calculated PFD

avg

and PFH values are within the

allowed range for SIL 2 according to table 2 / 3 of IEC 61508-1 and do fulfill the requirement to not
claim more than 35% of this range, i.e. to be better than or equal to 3.50E-03 respectively
3.50E-07 1/h.
The boxes marked in dark grey indicate that the PFD

avg

respectively the PFH values do not fulfill

the requirements for SIL 2 of table 2 / 3 of IEC 61508-1.

Failure category

SFF PFD

avg

at T

proof

=

PFH

SIL AC

λ

SD

λ

SU

λ

DD

λ

DU

[FIT]

[%]

1 year

2 years

5 years

10 years

Close

coupled low

stress

0

146 483

41

93.9

2.07E-04

3.85E-04

9.18E-04

1.81E-03

4.10E-08

SIL 2

Close

coupled high

stress

0

146 2291

57

97.7

3.27E-04

5.74E-04

1.35E-03

2.55E-03

5.70E-08

SIL 2

Extension

wires low

stress

0

146 1329

50

96.7

2.71E-04

4.87E-04

1.14E-03

2.22E-03

5.00E-08

SIL 2

Extension

wires high

stress

0

146 19198

230

98.8

1.56E-03

2.56E-03

5.55E-03

1.05E-02

2.30E-07

(SIL 1)