SAFETY-RELATED CHARACTERISTICS
7
13
TT 51 SERIES
www.krohne.com
09/2010 - 4000869801 - AD TT 51 SIL R01 en
Safety-related characteristics
7.1 Assumptions
The following assumptions have been made during the Failure Modes, Effects and Diagnostic
Analysis of the HART
®
temperature transmitter TT 51 C&R SIL.
• Failure rates are constant, wear out mechanisms are not included.
• Propagation of failures is not relevant.
• External power failure rates are not included.
• The mean time to restoration (MTTR) after safe failure is 24 hours.
• For safety applications only the 4..20 mA output was considered. The HART
®
protocol at
TT 51 C&R is only used for setup and diagnostic purpose, not during safety operation mode.
• The failure rates of the electronic components used in this analysis are obtained from a
collection of industrial databases.
• The temperature transmitters with 4..20 mA output are considered to be type B subsystems
with a hardware fault tolerance of 0.
• The failure rates do not include failures resulting from incorrect use of the equipment.
• The HART
®
protocol is only used for setup, calibration and diagnostics purpose, not during
safety operation mode.